Eave and Gable Extensions
MVF-MVP Gable Ext Lead End w FSP Soffit
If sub-framing at gable extension exceeds 4'-0 spacing then an A-20 angle will be sent and field cut around purlins for attachment. Fasteners for angle to purlin and soffit to angle will be sent. Change angle and fasteners to "DIM" layer.
* NOTE: This fastener must not hit the purlin. ** Field cut around purlins for attachment.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
GABLE EXTENSION DIMENSION
BL
GABLE TRIM (GTVC)
DOUBLE BEAD TAPE MASTIC * 1/4-14 X 7/8" WT (6" C.C.)
PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)
(2) #12-14 X 1 1/4" EACH CLIP (WALL COLOR) (2) #12-14 X 1 1/4'' (WALL COLOR)
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) MVF/MVP ROOF PANEL ** RAKE ANGLE (A-20)
PANEL CLIP w/FASTENERS (TYP.) (SEE ROOF PANEL PLAN)
PURLIN
GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8"
PURLIN
***DRAFTING NOTE: Thermal spacer to be used with no insulation.
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN CLOSURE (GPC)
***
(2) #12-14 X 1 1/4"' PER CLOSURE
(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN #12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
TOP VIEW
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
GABLE EXPANSION TRIM (GET)
1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC)
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS)
EAVE STRUT
FSP SOFFIT PANEL
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
**** DRAFTING NOTE: Inside closure must be provided on buildings with Liner Insulation System.
1/8" X 3/8" BLIND RIVET (12" C.C.)
INSIDE CLOSURE ****
PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)
1/4-14 X 7/8" (12" C.C.)
PURLIN CLOSURE INSTALLATION
WALL PANEL