Eave and Gable Extensions
Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Oversize Gutter
* FIELD DRILL 1/4" DIA. HOLE IN GUTTER STRAP, FIELD DRILL 1/8" DIA. PILOT HOLE IN FLAT STRAP IF REQUIRED.
1
BL
PANEL CLIP WITH FASTENERS
1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT (AT STRAP LOCTIONS) DOUBLE BEAD TAPE MASTIC GUTTER STRAP (GSM) (2'-8" C.C AT PANEL HI-RIBS) * 1/4-14 X 1" (EACH STRAP) TAPE MASTIC
1/4-14 X 1 1/4" WT (4 PER PANEL)
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
INTERMEDIATE PURLIN
"PIG TAIL" TAPE MASTIC (BETWEEN PANELS) (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL
3 3
1/4-14 X 1 1/4" WT (4 PER PANEL) MVF-MVP ROOF PANEL
8 "
EAVE STRUT
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
FLAT STRAP (PL- )
SPECIAL EAVE GUTTER (SPT-) #12-14 X 1 1/4" (TRIM COLOR) 1/8" x 3/8" BLIND RIVET (7-0" C.C.)
**
INSIDE CLOSURE
OUTSIDE CLOSURE
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)
SOFFIT PURLIN
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (SBLTA) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)
FSP SOFFIT PANEL
TRIM CAP (TCM)
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/8" X 3/8" BLIND RIVET (12" C.C.) (TYP.) EAVE EXTENSION PURLIN
SPECIAL TRIM (SPT- )
NOTE: 26 GA FSP SOFFIT MUST HAVE 1/4-14 X 7/8" FASTENERS AT HI-RIB, LOCATED AT SUPPORTS AND MID-SPAN BETWEEN SUPPORTS. SHOW AND CALL OUT FASTENER IF REQUIRED. NOTE: SOFFIT PURLIN SHOWN REMOVE IF NOT USED. TURN SPECIAL ANGLE FASTENER & TEXT TO BE VISIBLE.
WALL PANEL
SPECIAL ANGLE (PL )
** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.