Eave and Gable Extensions

STC-MSC Low Side Eave Ext w Oversize Gutter and FSP Soffit and Thermal Spacer

METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT (8 PER PANEL) ** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

* TRAPEZOID PLUG (TRP) AT EACH HIGH RIB

BL

1/4-14 X 7/8" WT (6" C.C.) (1/4-14 X 1" AT STRAP LOCATION) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) GUTTER STRAP (GSM) AT PANEL HI-RIBS *** 1/4-14 X 1" (EACH STRAP)

PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION (NOT BY CHIEF)

PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

#12-14 X 1" PANCAKE HEAD (12" C.C.)

STC/MSC ROOF PANEL

#12-14 X 1 1/4" (EACH STRAP) (TRIM COLOR)

1/4-14 X 1 1/4" WT (6 PER PANEL)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (SBLTO) OUTSIDE CLOSURE #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE ****

INTERMED. PURLIN *****

WALL PANEL

FLAT STRAP (GSMO-)

OVERSIZE GUTTER (SPT- )

EAVE EXTENSION FLASHING (EEFA)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.)

FSP SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)

PANEL OVERHANG

GUTTER STRAP LAP

PITCH

<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12 ALL DIMENSIONS IN INCHES 4 1/2 3 1/2 3 1/2 4 4 1/4

7 7/8 7 1/2

#12-14 X 1" PANCAKE HEAD (12" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

*******

7 1/8

#12-14 X 1" PANCAKE HEAD (12" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)

6 7/16

*** Field drill 1/4" dia. hole in gutter strap, field drill 1/8" dia. pilot hole in flat strap if required. ** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. * See isometric Trapezoid Plug Installation detail for installation instructions.

5 3/4

DRAFTING NOTES: **** Inside closure must be provided on buildings with liner insulation system. ***** If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer. ****** 26 GA FSP soffit must always have 1/4-14 x 7/8" fasteners located at ribs at end supports. change fasteners to "dim" layer.