Eave and Gable Extensions
STC-MSC Gable Ext Tail End w NO Soffit
* NOTE: It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
GABLE TRIM (GTMC)
PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN)
GABLE EXTENSION DIMENSION TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-S)
BL
PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)
PURLIN
#12-14 X 1" PANCAKE HEAD
STC/MSC ROOF PANEL
PURLIN CLOSURE (GPC) PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)
(2) #12-14 X 1 1/4"' PER CLOSURE
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
(2)1/4-14 X 7/8"
TOP VIEW
1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN) #12-14 X 1 1/4" (12" C.C.)
PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
INSIDE CLOSURE **
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW
EAVE STRUT
WALL PANEL
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION
PURLIN CLOSURE INSTALLATION
Made with FlippingBook flipbook maker