Eave and Gable Extensions

STC-MSC Gable Ext Tail End w NO Soffit

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM)

1

GABLE EXTENSION DIMENSION TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PANEL CLIP w/FASTENERS

BL

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

PURLIN

#12-14 X 1" PANCAKE HEAD

STC/MSC ROOF PANEL

PURLIN CLOSURE (GPC) PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF)

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

(2)1/4-14 X 7/8"

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

TOP VIEW

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) GABLE EXPANSION TRIM (GET) #12-14 X 1" PANCAKE HEAD EACH PURLIN) #12-14 X 1 1/4" (12" C.C.)

INSIDE CLOSURE **

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW

EAVE STRUT

WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PURLIN CLOSURE INSTALLATION