Eave and Gable Extensions

STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w NO Soffit

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

1

GABLE EXTENSION DIMENSION

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PURLIN CLOSURE (GPC)

PURLIN

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.)

PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF)

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN

STC/MSC ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1" PANCAKE HEAD PANEL CLIP w/FASTENERS

**

TOP VIEW

INSIDE CLOSURE

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

PURLIN

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EAVE STRUT

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

WALL PANEL

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PURLIN CLOSURE INSTALLATION