Eave and Gable Extensions

STC-MSC Gable Ext Tail End-Field Bend Vertical Leg-Term Trim w FSP Soffit

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

1

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) (TYP. AT GEC) RAKE SUPPORT (A-20-S) **1/4-14 X 1 1/4 SHOULDER (24" C.C.)

PANEL CLIP w/FASTENERS

PURLIN

PURLIN

STC/MSC ROOF PANEL

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *** DRAFTING NOTE: *** (NOT BY CHIEF) THERMAL SPACER TO BE USED WITH NO INSULATION

GABLE TRIM (GTM)

**** RAKE ANGLE (A-20) RAKE ANGLE (A-20-B)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

RAKE SUPPORT (A-20-S)

(2) #12-14 X 1 1/4"' PER CLOSURE

* 1/4-14 X 1 1/4 SHOULDER (24" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

PURLIN CLOSURE (GPC)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2)1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

GABLE TRIM SUPPORT (GTS) 10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.)

GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

1/4-14 X 7/8" (12" C.C.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION EXTENSION FLASHING (EF) GABLE EXTENSION CHANNEL (GEC)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION (TYP.) JAMB TRIM/SOFFIT TRIM (JTS)

EAVE STRUT

INSIDE CLOSURE **

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

FSP SOFFIT PANEL

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

1/8" X 3/8" BLIND RIVET (12" C.C.)

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

**** FIELD CUT AROUND PURLINS FOR ATTACHMENT

PURLIN CLOSURE INSTALLATION

WALL PANEL