Eave and Gable Extensions

STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w FSP Soffit and Thermal Spacer

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

* NOTE: It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

PANEL CLIP w/FASTENERS (TYP) (SEE ROOF PANEL PLAN) PURLIN THERMAL SPACER STC/MSC ROOF PANEL (NOT BY CHIEF)

GABLE TRIM (GTMC)

PURLIN

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN CLOSURE (GPC)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

TOP VIEW

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

GABLE EXTENSION CHANNEL (GEC)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) INSIDE CLOSURE ***

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

FSP SOFFIT PANEL

1/8" X 3/8" BLIND RIVET (12" C.C.)

WALL PANEL

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

** RAKE ANGLE (A-20)

PURLIN CLOSURE INSTALLATION

** FIELD CUT AROUND PURLINS FOR ATTACHMENT.