Eave and Gable Extensions
STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w FSP Soffit and Thermal Spacer
IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.
* NOTE: It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
GABLE EXTENSION DIMENSION
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
BL
NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)
PANEL CLIP w/FASTENERS (TYP) (SEE ROOF PANEL PLAN) PURLIN THERMAL SPACER STC/MSC ROOF PANEL (NOT BY CHIEF)
GABLE TRIM (GTMC)
PURLIN
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN CLOSURE (GPC)
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
(2) #12-14 X 1 1/4"' PER CLOSURE
(2) 1/4-14 X 7/8"
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
TOP VIEW
GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)
1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
GABLE EXTENSION CHANNEL (GEC)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)
EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)
1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) INSIDE CLOSURE ***
EAVE STRUT
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
FSP SOFFIT PANEL
1/8" X 3/8" BLIND RIVET (12" C.C.)
WALL PANEL
*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.
** RAKE ANGLE (A-20)
PURLIN CLOSURE INSTALLATION
** FIELD CUT AROUND PURLINS FOR ATTACHMENT.
Made with FlippingBook flipbook maker