Eave and Gable Extensions

STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w FSP Soffit and Thermal Spacer

PANEL CLIP w/FASTENERS (TYP) WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER. IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

1

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTM) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

PURLIN THERMAL SPACER STC/MSC ROOF PANEL

PURLIN

(NOT BY CHIEF)

PURLIN CLOSURE (GPC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

TOP VIEW

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

GABLE EXTENSION CHANNEL (GEC)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) INSIDE CLOSURE ***

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

FSP SOFFIT PANEL

WALL PANEL

1/8" X 3/8" BLIND RIVET (12" C.C.)

JAMB TRIM/SOFFIT TRIM (JTS)

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

** RAKE ANGLE (A-20)

PURLIN CLOSURE INSTALLATION

** FIELD CUT AROUND PURLINS FOR ATTACHMENT.