High Profile Trim

STC-MSC Gable Ext Tail End High Profile Trim-CS Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH) 1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) ** EXTENSION FLASHING (EFCP) (2) 1/4-14 X 7/8"

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *1/4-14 X 1 1/4" SHOULDER (24" C.C.)

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

PURLIN

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE (GPC)

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

EAVE STRUT

TRIM TYPE EFCP ECHP

L OR H SYSTEM

PURLIN SIZE

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC / MSC

***

INSIDE CLOSURE

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

8

HIGH HIGH

JAMB TRIM (JT)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

10

EFCP = EXTENSION FLASHING HIGH PROFILE ECHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION

WALL PANEL