High Profile Trim

MVF-MVP Gable Ext Tail End w High Profile Trim-AP Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

ROOF PANEL CUT BACK DIMENSION

* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN.

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

* 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" PANEL CLIP w/FASTENERS ** GABLE TRIM (GTVH) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP CLIP LOCATION FROM SL PANEL SUPPORT TRIM (SSP)

PURLIN

1 3

PANEL CLIP w/FASTENERS

4 "

THERMAL SPACER

(NOT BY CHIEF)

1"

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)

PURLIN

MVF/MVP ROOF PANEL PURLIN CLOSURE (GPC)

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN #12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

(2) #12-14 X 1 1/4"' PER CLOSURE

TOP VIEW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

AP SOFFIT PANEL

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) PANEL SUPPORT TRIM (SSP)

INSIDE CLOSURE ***

EAVE STRUT

JAMB TRIM (JT)

PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20-B)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

HIGH PROFILE TRIM-SOFFITED GABLE EXT MVF/MVP

TRIM TYPE EGFA EFHP

PURLIN SIZE

L OR H SYSTEM

#12-14 X 1" PANCAKE HEAD EACH PURLIN

8

HIGH HIGH

WALL PANEL

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

10

1/4-14 X 7/8" (12" C.C.) (TYP.)

PURLIN CLOSURE INSTALLATION

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

Made with FlippingBook flipbook maker