MVF MVP Roof Panel

MVF-MVP Inset Gable Lead End Height Change w Cut Roof Panel and Panel Below

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

L ROOF PANEL CUT BACK DIM. CLIP LOCATION FROM B

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

*WALL PANEL INSIDE CLOSURE #12-14 X 1 1/4"

TAPE MASTIC HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT)

BL

2 1 4 "

(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1 1 2 "

DOUBLE BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (12" C.C.)** (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR

PURLIN

RAKE ANGLE (A-20-L)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

MVF/MVP ROOF PANEL RAKE ANGLE (A-20-B)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN

1

4 "

***

TOP VIEW

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

PANEL CLIP

DOUBLE BEAD TAPE MASTIC

PANEL CLIP w/FASTENERS (REFER TO ROOF PANEL PLAN)

(2) #12-24 X 1 1/2" (36" C.C.) RAKE ANGLE (A-20) HEIGHT CHANGE RAFTER **NOTE: This fastener must not hit the purlin. #12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

(2) #12-14 X 1 1/4"

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANELING CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.)

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PURLIN CLOSURE INSTALLATION