MVF MVP Roof Panel

MVF-MVP Inset Gable Tail End Height Change w Cut Roof Panel and Panel Below-Thermal Spacer

ROOF PANEL CUT BACK DIM. CLIP LOCATION FROM B

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

L

CLOSURE CLIPS (GCC-1) (TYP.)

BL

TAPE MASTIC HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT)

PURLIN CLOSURE (TYP.)

2 1 4 "

*WALL PANEL INSIDE CLOSURE #12-14 X 1 1/4"

1 1 2 "

1/4-14 X 1 1/4" WT (12" C.C.)** RAKE ANGLE (A-20-B) DOUBLE BEAD TAPE MASTIC (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR

(6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-L)

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

MVF/MVP ROOF PANEL

(NOT BY CHIEF)

THERMAL SPACER

TOP VIEW

1

4 "

PANEL CLIP w/FASTENERS (REFER TO ROOF PANELING PLAN)

DOUBLE BEAD TAPE MASTIC

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

#12-14 1 1/4" (2 EACH PURLIN) (WALL COLOR)

HEIGHT CHANGE RAFTER

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

EAVE STRUT

(2) #12-24 X 1 1/2" (36" C.C.)

1/4-14 X 7/8" (12" C.C.) PANELING CAP TRIM (SCT)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

RAKE ANGLE (A-20)

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

PURLIN CLOSURE INSTALLATION

**NOTE: This fastener must not hit the purlin.