MVF MVP Roof Panel
MVF-MVP Outset Gable Lead End Height Change and Panel Below-Thermal Spacer
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.
PURLIN CLOSURE (TYP.)
HEIGHT CHANGE TRIM BOTTOM (GHVB) HEIGHT CHANGE TRIM TOP (GHVT)
BL
*WALL PANEL INSIDE CLOSURE #12-14 X 1 1/4"
PURLIN
MVF/MVP ROOF PANEL DOUBLE BEAD TAPE MASTIC 1/4-14 X 7/8" WT (12" C.C.)** TAPE MASTIC (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-L)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
(2) #12-14 X 1 1/4"' PER CLOSURE
TOP VIEW
1
4 "
THERMAL SPACER
(NOT BY CHIEF)
PANEL CLIP
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR)
1"
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
PANEL CLIP w/FASTENERS (REFER TO ROOF PANELING PLAN)
#12-14 X 1 1/4" (GA) (2 EACH PURLIN)
(2) #12-14 X 1 1/4"
EAVE STRUT
RAKE ANGLE (A-20)
PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)
HEIGHT CHANGE RAFTER
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
**NOTE: This fastener must not hit the purlin.
PANELING CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.)
PURLIN CLOSURE INSTALLATION