Wall Panel and Trim
Animated publication
Wall Panel and Trim Sections & Details
All details downloadable in .dwg and .pdf
Table of Contents
Wall Panel Details AP Wall Details CS Wall Details AP Panel Openings AP Metal Bldg Walkdoor-KD-Others AP Metal Bldg Walkdoor-PA-SF AP OHD or 3-Sided Opening AP Window by Chief
AP Window or 4-Sided Opening w Jamb Trim–JT AP Window or 4-Sided Opening w Sill Flashing–WFS AP Trim Only 4-Sided Opening w Jamb Trim-JT AP Trim Only 4-Sided Opening w Sill Flashing-WFS CS Panel Openings CS Metal Bldg Walkdoor-KD-Others CS Metal Bldg Walkdoor-PA-SF CS OHD or 3-Sided Opening CS Window by Chief CS Window or 4-Sided Opening w Jamb Trim-JT CS Window or 4-Sided Opening w Sill Flashing-WFS CS Trim Only 4-Sided Opening w Jamb Trim-JT CS Trim Only 4-Sided Opening w Sill Flashing-WFS Wainscot - Lapped T19.Wainscot Lapped at Zee w A-20
T21.Wainscot Lapped HRC T22.Wainscot Lapped Zee Wainscot Lapped at Sill
Wainscot Lapped Mid-wall at Cee Wainscot Lapped Mid-wall at Zee Wainscot - No Lap (w WTT Trim)
T15.Wainscot No Lap WTT at Cee T17.Wainscot No Lap WTT at HRC T18.Wainscot No Lap WTT at Zee Wainscot No Lap WTT at Sill w Window by Chief
Wainscot No Lap WTT Mid-Wall at Cee Wainscot No Lap WTT Mid-Wall at Zee Base Conditions Base Trim NONE-Lap
Base Trim NONE-No Lap Base Trim NONE-Notch Base Trim Simple L BT-Lap
Table of Contents
Base Trim Simple L BT-No Lap Base Trim Simple L BT-Notch Base Trim w Drip Edge BTN-Lap Base Trim w Drip Edge BTN-No Lap Base Trim w Drip Edge BTN-Notch
Base Trim w Drip Edge Vertical BTNV-Lap Base Trim w Drip Edge Vertical BTNV-No Lap Base Trim w Drip Edge Vertical BTNV-Notch Base Trim w Return Leg BTM-Lap Base Trim w Return Leg BTM-No Lap Base Trim One Piece OPB Wallite Light Transmitting Panel
AP Wall AP Light Transmitting Panel w AP Liner Panel Horizontal Section AP Wall AP Light Transmitting Panel w CS Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w AP Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w CS Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w Full Height Liner CS Wall CS Light Transmitting Panel w AP Liner Panel Horizontal Section CS Wall CS Light Transmitting Panel w CS Liner Panel Horizontal Section CS Wall-CS Light Transmitting Panel or AP Wall-AP LTP w Full Height Liner
Wall Panel Details
Wall Panel Details
AP Wall Details
AP WALL PANEL - The details shown below are typical Chief metal building details. Not all details may apply. Specific details for additional features will be provided for complete installation instructions.
12"
NOTES: · The structural system must be plumb and square prior to panel installation. · Care must be taken to insure panel modularity due to accessory locations and trim. · Insulation has not been shown for clarity. · Blanket insulation must be trimmed above the bottom of panel to prevent water from "WICKING" into the insulation. · Provide air gap of 1/4” min. at bottom of panel to avoid corrosion. · #12-14 X 1 1/4" Fastener spacing is (12" C.C.) unless otherwise noted. ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness ** #12-14 X 2", Blanket Insulation >4" thickness · When possible, CHIEF recommends installing panel so that panel lap is away from prevailing weather.
Top of wall panel is held down 1" from eave height. (Except MSC 2" offset clip, the dimension is 0")
STEEL LINE
BL
GIRT
Clip offset
RAKE ANGLE
WALL PANEL
TAPE MASTIC AT SIDELAPS, IF ORDERED ** #12-14 X 1 1/4 (12" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
TOP OF PURLIN
NOTE: Field cut ends of wall panels above roof line as required on slopes greater than 1 1/4:12.
**#12-14 X 1 1/4" (12" C.C.)
1"
BL
AP PANELING
Intermediate Girt Detail
STEEL LINE
Eave Height
BL
EAVE STRUT
WALL PANEL
BL
PANEL SIDELAP EAVE STRUT
Sidewall Eave Detail Low side shown. High Side Typical.
** #12-14 X 1 1/4" (12" C.C.) (TYP.)
GIRT
12" (TYP.)
RISE
3" 3"
6"
MIN.
**#12-14 X 1 1/4" (12" C.C.)
WALL PANEL
BL
Panel Endlap Detail
* 1/4-14 X 7/8" (TYP.)
AP PANEL FASTENER INSTALLATION
AP PANEL AT GABLE END
1/4-14 X 7/8" (TYP.) (18" C.C.)
NOTE: · Sidelap holes (7/32" DIA.) must be Pre-drilled in the overlapping corrugation only. · The overlapping corrugation does not have the return leg.
NOTES: ·
Field cut panel if required for corner trim.
· Corner Angle connection/fasteners, refer to Girt Corner Detail.
GIRT
12" (TYP.)
SHEETING SUPPORT (SSP)
TAPE MASTIC CENTERED ON HIGH RIB IS SHOWN THOUGH IS AN ORDER OPTION. REFER TO WALL MASTIC REQUIREMENTS IN ORDERED OPTIONS ON DRAWING COVER PAGE (C1)
1/4-14 X 7/8" (18" C.C.)
** #12-14 X 1 1/4" (12" C.C.) (TYP.)
STEEL LINE
CORNER TRIM (CTA)
RETURN LEG
L
B
* 18" (TYP.)
CORNER ANGLE (A-20)
PRE-DRILL PILOT HOLE IN OVERLAPPING PANEL (SEE NOTE)
12" (TYP.)
AP PANEL 1/4-14 X 7/8" (12" C.C.) (TYP.)
** #12-14 X 1 1/4" (12" C.C.) (TYP.)
2 1/2"
2 1/2"
1 1/2"
BASE MEMBER
TAPE MASTIC AT SIDELAPS, IF ORDERED
B
L
AP PANEL INSTALLATION
AP PANEL SIDE LAPS
AP PANEL STANDARD CORNER CONDITION
CS Wall Details
CS WALL PANEL - The details shown below are typical Chief metal building details. Not all details may apply. Specific details for additional features will be provided for complete installation instructions.
6"
3"
NOTES: · The structural system must be plumb and square prior to panel installation. · Care must be taken to insure panel modularity due to accessory locations and trim. · Insulation has not been shown for clarity. · Blanket insulation must be trimmed above the bottom of panel to prevent water from "WICKING" into the insulation. · Provide air gap of 1/4” min. at bottom of panel to avoid corrosion. · #12-14 X 1 1/4" Fastener spacing is (12" C.C.) unless otherwise noted. ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness ** #12-14 X 2", Blanket Insulation >4" thickness · When possible, CHIEF recommends installing panel so that panel lap is away from prevailing weather.
Top of wall panel is held down 1" from eave height. (Except MSC 2" offset clip, the dimension is 0")
STEEL LINE
GIRT
Clip offset
WALL PANEL
RAKE ANGLE
TAPE MASTIC AT SIDELAPS, IF ORDERED ** #12-14 X 1 1/4 (6" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
TOP OF PURLIN
NOTE: Field cut ends of wall panels above roof line as required on slopes greater than 1 1/4:12.
**#12-14 X 1 1/4" (6" C.C.)
1"
BL
CS PANELING
Intermediate Girt Detail
STEEL LINE
Eave Height
EAVE STRUT
WALL PANEL
BL
PANEL SIDELAP EAVE STRUT
Sidewall Eave Detail Low side shown. High Side Typical.
GIRT
6" (TYP.)
3"
** #12-14 X 1 1/4" (6" C.C.) (TYP.)
RISE
3" 3"
6"
MIN.
**#12-14 X 1 1/4" (6" C.C.)
WALL PANEL
BL
1/4-14 X 7/8" (TYP.) (18" C.C.)
Panel Endlap Detail
* 1/4-14 X 7/8" (TYP.)
CS PANEL FASTENER INSTALLATION
CS PANEL AT GABLE END
NOTE: · Sidelap holes (7/32" DIA.) must be Pre-drilled in the overlapping corrugation only. · The overlapping corrugation does not have the return leg.
NOTES: ·
Field cut panel if required for corner trim.
· Corner Angle connection/fasteners, refer to Girt Corner Detail. · Connection of panel to structure at corner is by the corner trim fasteners.
GIRT
12" (TYP.)
** #12-14 X 1 1/4" (12" C.C.) (TYP.)
1/4-14 X 7/8" (18" C.C.)
CORNER TRIM (CT)
STEEL LINE
CORNER ANGLE (A-20)
RETURN LEG
PRE-DRILL PILOT HOLE IN OVERLAPPING PANEL (SEE NOTE)
* 18" (TYP.)
L
B
TAPE MASTIC CENTERED ON HIGH RIB IS SHOWN THOUGH IS AN ORDER OPTION. REFER TO WALL MASTIC REQUIREMENTS IN ORDERED OPTIONS ON DRAWING COVER PAGE (C1)
6" (TYP.)
3"
CS PANEL
* 1/4-14 X 7/8" (TYP.)
** #12-14 X 1 1/4" (6" C.C.) (TYP.)
2 1/2"
1 1/2"
#12-14 X 1 1/4 (12" C.C.) (TYP.)
BASE MEMBER
B
L
CS PANEL INSTALLATION
CS PANEL SIDE LAPS
CS PANEL STANDARD CORNER CONDITION
AP Panel Openings
AP Panel Openings
AP Metal Bldg Walkdoor-KD-Others
AP Panel - Metal Building Walkdoor -- Knocked-Down (by Chief) or Door Not by Chief Refer to Order Documents for Doors by Chief
Installation Steps: 1. Install Wrap Plate. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Door. 4. Sheeting Support (SSP) 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.
Head Trim (HTT) lapped 4 1/4" min. past edge of door frame. Flush with end of Jamb Trim (JTA).
INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)
2 1/4" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
2" PANEL SLIT
SHEETING SUPPORT (SSP)
· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)
2" SLIT
2 1/4" X 1/4" NOTCH
WALL PANEL
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
JAMB TRIM (JTA)
DOOR JAMB
DOOR FRAME
EDGE OF DOOR FRAME FLAT OF HEAD TRIM
JAMB TRIM (JTA)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
WALL PANEL
#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)
BL
OPENING WIDTH
**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
ZEE GIRT
JAMB
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)
NOMINAL DOOR OPENING
**#12-14 X 1 1/4" (12" C.C.)
* 1 4 "
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)
DOOR FRAME
BL
1
2 " MIN.
CUT RIB AS NEEDED
SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)
***1/8"-3/4"
DOOR FRAME
OPENING HEIGHT
NOMINAL
DOOR OPENING
*** Locate JTA/SSP trim to cover door frame avoiding interference with latch, door and hinges.
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
JAMB TRIM (JTA)
CEE HEADER
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
AP Metal Bldg Walkdoor-PA-SF
AP Panel- Metal Building Walkdoor - Pre-Assembled (by Chief) or Self-Framing Not by Chief Refer to Order Documents for Doors Supplied by Chief
Installation Steps: 1. Install Wrap Plate. 2. Door. 3. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Sheeting Support (SSP) 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.
Head Trim (HTT) lapped 4 1/4" min. past edge of door frame. Flush with end of Jamb Trim (JTA).
INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)
2 1/4" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
2" PANEL SLIT
SHEETING SUPPORT (SSP)
· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)
2" SLIT
WALL PANEL
2 1/4" X 1/4" NOTCH
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
JAMB TRIM (JTA)
DOOR JAMB
DOOR FRAME
EDGE OF DOOR FRAME FLAT OF HEAD TRIM
JAMB TRIM (JTA)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.)
WALL PANEL
#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)
BL
OPENING WIDTH
**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
ZEE GIRT
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)
DOOR SUB FRAME
NOMINAL DOOR OPENING
**#12-14 X 1 1/4" (12" C.C.)
* 1 4 "
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)
DOOR FRAME
BL
1
2 " MIN.
CUT RIB AS NEEDED
SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)
***1/8"-3/4"
DOOR FRAME
OPENING HEIGHT
NOMINAL
DOOR OPENING
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
*** Locate JTA/SSP trim to cover door frame avoiding interference with latch, door and hinges.
JAMB TRIM (JTA)
CEE HEADER
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
AP OHD or 3-Sided Opening
AP Panel - OHD or 3-Sided Opening
Installation Steps: 1. Door Trim (DT), if applicable. 2. Sheeting Support (SSP) 3. Header Trim (HTT). 4. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.
INSIDE CLOSURE
Head Trim (HTT) lapped 4 1/4" min. past edge of door jamb. Flush with end of Jamb Trim (JTA).
Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP)
· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
2" PANEL SLIT
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)
WALL PANEL
2" X 1/4" NOTCH
2" SLIT
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
DOOR JAMB JAMB TRIM (JTA)
DOOR TRIM (DT)
EDGE OF DOOR JAMB FLAT OF HEAD TRIM
JAMB TRIM (JTA)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS 1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.)
WALL PANEL
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE
JAMB
**#12-14 X 1 1/4" (12" C.C.)
HEADER
2 1/4"
HEADER TRIM (HTT)
* 1 4 "
BL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)
DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
OPENING HEIGHT
JAMB TRIM (JTA)
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
AP Window by Chief
AP Panel - Window by Chief
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Window 5. Sill Jamb Trim (JT), slit and fold up at jamb. 6. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA) Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).
INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP)
2" PANEL SLIT
WALL PANEL
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)
JAMB TRIM (JTA)
LINER COVER TRIMS
2" SLIT
2" X 1/4" NOTCH
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
Optional urethane caulk at JT end. (NOT BY CHIEF)
4 1/4" TO EDGE OF WINDOW JAMB
Optional urethane caulk behind JT (NOT BY CHIEF)
SILL JAMB TRIM (JT) NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL
JAMB TRIM (JTA)
FLAT OF
EDGE OF JAMB HEAD TRIM
Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
LINER COVER TRIM (LCT1)
**#12-14 X 1 1/4" (12" C.C.)
CEE HEADER
INSIDE CLOSURE
2 1 4 "
* 1 4 "
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
HEADER TRIM (HTT) WINDOW BY CHIEF URETHANE CAULK (NOT BY CHIEF)
LINER COVER TRIM (LCT2)
JAMB
LINER COVER TRIM (LCT1)
SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT) * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
OPENING
URETHANE CAULK (NOT BY CHIEF) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY)
WALL PANEL
SILL JAMB TRIM (JT) URETHANE CAULK (NOT BY CHIEF)
JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)
GIRT/SILL
Optional urethane caulk behind JT (NOT BY CHIEF)
SHEETING SUPPORT (SSP)
1/8" x 3/8" BLIND RIVET (7'-0" C.C.)
WALL PANEL (TYP.)
CHIEF WINDOW HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
AP Window or 4-Sided Opening w Jamb Trim–JT
AP Panel - Window Not by Chief or 4-Sided Opening with Sill Jamb Trim – JT
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Sill Jamb Trim (JT), slit and fold up at jamb. 6. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).
INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL
2" PANEL SLIT
LINER COVER TRIMS
Optional Urethane caulk at JT end. (NOT BY CHIEF)
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)
2" SLIT
2" X 1/4" NOTCH
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
4 1/4" TO EDGE OF WINDOW JAMB
OPTIONAL JAMB TRIM FOLD AT END
SILL JAMB TRIM (JT) Optional urethane caulk behind JT (NOT BY CHIEF)
JAMB TRIM (JTA)
FLAT OF
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL
EDGE OF JAMB HEAD TRIM
Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
LINER COVER TRIM (LCT1)
**#12-14 X 1 1/4" (12" C.C.)
CEE HEADER
INSIDE CLOSURE
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
2 1 4 "
* 1 4 "
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
LINER COVER TRIM (LCT2)
HEADER TRIM (HTT) WINDOW BY CHIEF
JAMB
LINER COVER TRIM (LCT1)
SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
OPENING
**#12-14 X 1 1/4" (12" C.C.)
WALL PANEL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
SILL JAMB TRIM (JT)
INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)
SHEETING SUPPORT (SSP)
GIRT/SILL
WALL PANEL (TYP.) Optional urethane caulk behind JT (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
AP Window or 4-Sided Opening w Sill Flashing–WFS
AP Panel - Window Not by Chief or 4-Sided Opening with Sill Flashing – WFS
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
INSIDE CLOSURE
Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).
Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL
2" PANEL SLIT
LINER COVER TRIMS
FIELD VERIFY WFS OFFSET
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)
2" SLIT
2" X 1/4" NOTCH
Urethane sealant at WFS end (NOT BY CHIEF)
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
4 1/4" TO EDGE OF WINDOW JAMB
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)
JAMB TRIM (JTA)
FLAT OF
EDGE OF JAMB HEAD TRIM
Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
LINER COVER TRIM (LCT1)
INSIDE CLOSURE
CEE HEADER
2 1 4 "
* 1 4 "
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1/8" X 3/8" BLIND RIVET (3'-0" C.C.)
LINER COVER TRIM (LCT2)
HEADER TRIM (HTT)
JAMB
LINER COVER TRIM (LCT1)
GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
OPENING
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
WALL PANEL
JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
SHEETING SUPPORT (SSP)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
AP Trim Only 4-Sided Opening w Jamb Trim-JT
AP Panel - Trim Only 4-Sided Opening with Sill Jamb Trim – JT
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Jamb Trim (JT), slit and fold up at jamb. 4. Header Trim (HTT). 5. Sheeting Support (SSP) 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header and sill. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).
INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL
2" PANEL SLIT
Opitonal Urethane caulk at JT end. (NOT BY CHIEF) LINER COVER TRIMS
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)
REDUCE LEG LENGTH
2" SLIT
2" X 1/4" NOTCH
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
4 1/4" TO EDGE OF WINDOW JAMB
OPTIONAL JAMB TRIM FOLD AT END
SILL JAMB TRIM (JT)
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL Optional urethane caulk behind JT (NOT BY CHIEF)
JAMB TRIM (JTA)
FLAT OF
EDGE OF JAMB HEAD TRIM
Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
(Window not Shown)
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
FRAMING (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
LINER COVER TRIM (LCT1)
**#12-14 X 1 1/4" (12" C.C.)
FRAMING (NOT BY CHIEF)
INSIDE CLOSURE
2 1 4 "
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
* 1 4 "
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
LINER COVER TRIM (LCT2)
HEADER TRIM (HTT) WINDOW BY CHIEF
LINER COVER TRIM (LCT1)
SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
OPENING
**#12-14 X 1 1/4" (12" C.C.)
WALL PANEL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
SILL JAMB TRIM (JT)
INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)
SHEETING SUPPORT (SSP)
FRAMING (NOT BY CHIEF)
Urethane caulk behind JT (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
WALL PANEL (TYP.)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
AP Trim Only 4-Sided Opening w Sill Flashing-WFS
AP Panel - Trim Only 4-Sided Opening with Sill Flashing – WFS
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
INSIDE CLOSURE
Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).
Optional urethane caulk at HTT end. (NOT BY CHIEF)
HEADER TRIM (HTT)
2 1/4" X 1/4" PANEL NOTCH
SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL
2" PANEL SLIT
LINER COVER TRIMS
FIELD VERIFY WFS OFFSET
Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)
2" SLIT
2" X 1/4" NOTCH
Optional urethane sealant at WFS end (NOT BY CHIEF)
For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.
4 1/4" TO EDGE OF WINDOW JAMB
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)
JAMB TRIM (JTA)
FLAT OF
EDGE OF JAMB HEAD TRIM
Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)
END OF JAMB TRIM (JTA)
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
(Window not Shown)
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
FRAMING (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
LINER COVER TRIM (LCT1)
FRAMING (NOT BY CHIEF)
INSIDE CLOSURE
2 1 4 "
* 1 4 "
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1/8" X 3/8" BLIND RIVET (3'-0" C.C.)
LINER COVER TRIM (LCT2)
HEADER TRIM (HTT)
LINER COVER TRIM (LCT1)
GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
OPENING
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)
**#12-14 X 1 1/4" (12" C.C.)
WALL PANEL
JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)
CUT RIB AS NEEDED
SHEETING SUPPORT (SSP)
FRAMING (NOT BY CHIEF)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
CS Panel Openings
CS Panel Openings
CS Metal Bldg Walkdoor-KD-Others
CS Panel - Metal Building Walkdoor -- Knocked-Down (by Chief) or Door Not by Chief Refer to Order Documents for Doors by Chief
Installation Steps: 1. Install Wrap Plate. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Door. 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
1" PANEL SLIT
INSIDE CLOSURE
JAMB TRIM (JT)
For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
1" SLIT
2" X 1/4" NOTCH
2" JAMB TRIM NOTCH
COVER TRIM (COT)
DOOR FRAME
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
TRIM DETAIL AT CORNERS
WALL PANEL SLIT
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
WALL PANEL
#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)
BL
OPENING WIDTH
**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
ZEE GIRT
JAMB
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)
NOMINAL DOOR OPENING
* 1 4 "
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)
DOOR FRAME
BL
JAMB TRIM (JT)
1
2 " MIN.
WALL PANEL
CUT RIB AS NEEDED
***1/8"-3/4"
DOOR FRAME
OPENING HEIGHT
**#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)
NOMINAL
*** Locate JT/COT/HTT trim
DOOR OPENING
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
assembly to cover door frame avoiding interference with latch, door and hinges.
CEE HEADER
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
CS Metal Bldg Walkdoor-PA-SF
CS Panel- Metal Building Walkdoor - Pre-Assembled (by Chief) or Self-Framing Not by Chief Refer to Order Documents for Doors Supplied by Chief
Installation Steps: 1. Install Wrap Plate. 2. Door. 3. Jamb Trim (JT) with notch at header. 4. Header Trim (HTT). 5. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure. 7. Cover Trim (COT). 8. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
1" PANEL SLIT
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
INSIDE CLOSURE
For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
JAMB TRIM (JT)
1" SLIT
2" X 1/4" NOTCH
2" JAMB TRIM NOTCH
COVER TRIM (COT)
DOOR FRAME
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
WALL PANEL SLIT AND NOTCH (Typical at Sill)
TRIM DETAIL AT CORNERS
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
WALL PANEL
#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)
BL
OPENING WIDTH
**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
ZEE GIRT
DOOR SUBFRAME
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)
NOMINAL DOOR OPENING
* 1 4 "
LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)
DOOR FRAME
BL
JAMB TRIM (JT)
1
2 " MIN.
WALL PANEL
CUT RIB AS NEEDED
***1/8"-3/4"
DOOR FRAME
OPENING HEIGHT
**#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)
NOMINAL
*** Locate JT/COT/HTT trim
DOOR OPENING
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
assembly to cover door frame avoiding interference with latch, door and hinges.
CEE HEADER
WALKDOOR HEADER TRIM DETAILS
WALKDOOR JAMB TRIM DETAILS
CS OHD or 3-Sided Opening
CS Panel - OHD or 3-Sided Opening
Installation Steps: 1. Door Trim (DT), if applicable. 2. Jamb Trim (JT) with notch at header. 3. Header Trim (HTT). 4. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
HEADER TRIM (HTT)
1" PANEL SLIT
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
INSIDE CLOSURE
For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
JAMB TRIM (JT)
1" SLIT
2" X 1/4" NOTCH
2" JAMB TRIM NOTCH
DOOR TRIM (DT) OPTIONAL. REFER TO PANEL DRAWINGS.
COVER TRIM (COT)
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
WALL PANEL SLIT AND NOTCH (Typical at Sill)
TRIM DETAIL AT CORNERS
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)
WALL PANEL
BL
OPENING WIDTH
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE
JAMB
DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS
HEADER
1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
HEADER TRIM (HTT)
* 1 4 "
BL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)
JAMB TRIM (JT)
WALL PANEL **#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)
DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS
CUT RIB AS NEEDED
OPENING HEIGHT
For Walkdoors to avoidinterference with latch, door, or hinges, hold JT/COT/HTT trim assembly back from jamb max 3/4", as necessary
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
HEADER TRIM DETAILS
JAMB TRIM DETAILS
CS Window by Chief
CS Panel - Window by Chief
Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings.
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
3. Window with Bulbtite. 4. Sill Jamb Trim (JT). 5. Jamb Trim (JT) with notch at header. 6. Header Trim (HTT). 7. Notch and slit wall panel. 8. Place wall panel over trims with foam inside closures. 9. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
1" PANEL SLIT
JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)
LINER COVER TRIMS
For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
1" SLIT
2" X 1/4" NOTCH
3" TO FLAT OF JAMB TRIM
2" JAMB TRIM NOTCH
COVER TRIM (COT)
SILL JAMB TRIM (JT)
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
WALL PANEL SLIT (Typical at Sill)
TRIM DETAIL AT CORNERS
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)
BL
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY) JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (6" C.C.)
LINER COVER TRIM (LCT1)
CEE HEADER
INSIDE CLOSURE
OPENING WIDTH
* 1 4 "
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
HEADER TRIM (HTT) WINDOW BY CHIEF URETHANE CAULK (NOT BY CHIEF)
LINER COVER TRIM (LCT2)
LINER COVER TRIM (LCT1)
SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT) * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
**#12-14 X 1 1/4" (12" C.C.) WALL PANEL
OPENING
JAMB TRIM (JT)
CUT RIB AS NEEDED
URETHANE CAULK (NOT BY CHIEF)
1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)
URETHANE CAULK (NOT BY CHIEF)
SILL JAMB TRIM (JT) INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.)
GIRT/SILL
1/8" x 3/8" BLIND RIVET (7'-0" C.C.)
WALL PANEL (TYP.)
CHIEF WINDOW HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
CS Window or 4-Sided Opening w Jamb Trim-JT
CS Panel - Window Not by Chief or 4-Sided Opening with Sill Jamb Trim – JT
Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Jamb Trim (JT). 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closures. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
1" PANEL SLIT
JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)
LINER COVER TRIMS
For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
1" SLIT
2" X 1/4" NOTCH
3" TO FLAT OF JAMB TRIM
2" JAMB TRIM NOTCH
OPTIONAL JAMB TRIM FOLD AT END
COVER TRIM (COT)
SILL JAMB TRIM (JT) NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
WALL PANEL SLIT AND NOTCH (Typical at Sill)
TRIM DETAIL AT CORNERS
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.) **#12-14 X 1 1/4" (6" C.C.)
BL
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
LINER COVER TRIM (LCT1)
INSIDE CLOSURE
CEE HEADER
* 1 4 " * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
OPENING WIDTH
JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
HEADER TRIM (HTT)
LINER COVER TRIM (LCT2)
LINER COVER TRIM (LCT1)
SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
**#12-14 X 1 1/4" (12" C.C.) WALL PANEL
JAMB TRIM (JT)
OPENING
CUT RIB AS NEEDED
1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)
1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)
SILL JAMB TRIM (JT) INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.)
GIRT/SILL
1/8" x 3/8" BLIND RIVET (7'-0" C.C.)
WALL PANEL (TYP.)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
CS Window or 4-Sided Opening w Sill Flashing-WFS
CS Panel - Window Not by Chief or 4-Sided Opening with Sill Flashing – WFS
Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).
Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closures. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.
2" JAMB TRIM NOTCH
2" X 1/4" PANEL NOTCH
1" PANEL SLIT
JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)
LINER COVER TRIMS
FIELD VERIFY WFS OFFSET
For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.
1" SLIT
2" X 1/4" NOTCH
3" TO FLAT OF JAMB TRIM
2" JAMB TRIM NOTCH
COVER TRIM (COT)
NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)
Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)
FLAT OF JAMB TRIM FLAT OF HEAD TRIM
WALL PANEL SLIT AND NOTCH (Typical at Sill)
TRIM DETAIL AT CORNERS
(Window not Shown)
ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)
BL
1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)
1/8" X 3/8" BLIND RIVET (7'-0" C.C.)
**#12-14 X 1 1/4" (6" C.C.)
LINER COVER TRIM (LCT1)
INSIDE CLOSURE
CEE HEADER
* 1 4 "
* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1/8" X 3/8" BLIND RIVET (3'-0" C.C.)
OPENING WIDTH
JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)
LINER COVER TRIM (LCT2)
HEADER TRIM (HTT)
LINER COVER TRIM (LCT1)
GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)
BL
**#12-14 X 1 1/4" (12" C.C.) WALL PANEL
JAMB TRIM (JT)
OPENING
1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)
CUT RIB AS NEEDED
1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)
OPENING DETAILS AT HEADER AND SILL
FRAMED OPENING DETAILS AT JAMB
Made with FlippingBook - professional solution for displaying marketing and sales documents online