Wall Panel and Trim

Animated publication

Wall Panel and Trim Sections & Details

All details downloadable in .dwg and .pdf

Table of Contents

Wall Panel Details AP Wall Details CS Wall Details AP Panel Openings AP Metal Bldg Walkdoor-KD-Others AP Metal Bldg Walkdoor-PA-SF AP OHD or 3-Sided Opening AP Window by Chief

AP Window or 4-Sided Opening w Jamb Trim–JT AP Window or 4-Sided Opening w Sill Flashing–WFS AP Trim Only 4-Sided Opening w Jamb Trim-JT AP Trim Only 4-Sided Opening w Sill Flashing-WFS CS Panel Openings CS Metal Bldg Walkdoor-KD-Others CS Metal Bldg Walkdoor-PA-SF CS OHD or 3-Sided Opening CS Window by Chief CS Window or 4-Sided Opening w Jamb Trim-JT CS Window or 4-Sided Opening w Sill Flashing-WFS CS Trim Only 4-Sided Opening w Jamb Trim-JT CS Trim Only 4-Sided Opening w Sill Flashing-WFS Wainscot - Lapped T19.Wainscot Lapped at Zee w A-20

T21.Wainscot Lapped HRC T22.Wainscot Lapped Zee Wainscot Lapped at Sill

Wainscot Lapped Mid-wall at Cee Wainscot Lapped Mid-wall at Zee Wainscot - No Lap (w WTT Trim)

T15.Wainscot No Lap WTT at Cee T17.Wainscot No Lap WTT at HRC T18.Wainscot No Lap WTT at Zee Wainscot No Lap WTT at Sill w Window by Chief

Wainscot No Lap WTT Mid-Wall at Cee Wainscot No Lap WTT Mid-Wall at Zee Base Conditions Base Trim NONE-Lap

Base Trim NONE-No Lap Base Trim NONE-Notch Base Trim Simple L BT-Lap

Table of Contents

Base Trim Simple L BT-No Lap Base Trim Simple L BT-Notch Base Trim w Drip Edge BTN-Lap Base Trim w Drip Edge BTN-No Lap Base Trim w Drip Edge BTN-Notch

Base Trim w Drip Edge Vertical BTNV-Lap Base Trim w Drip Edge Vertical BTNV-No Lap Base Trim w Drip Edge Vertical BTNV-Notch Base Trim w Return Leg BTM-Lap Base Trim w Return Leg BTM-No Lap Base Trim One Piece OPB Wallite Light Transmitting Panel

AP Wall AP Light Transmitting Panel w AP Liner Panel Horizontal Section AP Wall AP Light Transmitting Panel w CS Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w AP Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w CS Liner Panel Horizontal Section AP Wall CS Light Transmitting Panel w Full Height Liner CS Wall CS Light Transmitting Panel w AP Liner Panel Horizontal Section CS Wall CS Light Transmitting Panel w CS Liner Panel Horizontal Section CS Wall-CS Light Transmitting Panel or AP Wall-AP LTP w Full Height Liner

Wall Panel Details

Wall Panel Details

AP Wall Details

AP WALL PANEL - The details shown below are typical Chief metal building details. Not all details may apply. Specific details for additional features will be provided for complete installation instructions.

12"

NOTES: · The structural system must be plumb and square prior to panel installation. · Care must be taken to insure panel modularity due to accessory locations and trim. · Insulation has not been shown for clarity. · Blanket insulation must be trimmed above the bottom of panel to prevent water from "WICKING" into the insulation. · Provide air gap of 1/4” min. at bottom of panel to avoid corrosion. · #12-14 X 1 1/4" Fastener spacing is (12" C.C.) unless otherwise noted. ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness ** #12-14 X 2", Blanket Insulation >4" thickness · When possible, CHIEF recommends installing panel so that panel lap is away from prevailing weather.

Top of wall panel is held down 1" from eave height. (Except MSC 2" offset clip, the dimension is 0")

STEEL LINE

BL

GIRT

Clip offset

RAKE ANGLE

WALL PANEL

TAPE MASTIC AT SIDELAPS, IF ORDERED ** #12-14 X 1 1/4 (12" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

TOP OF PURLIN

NOTE: Field cut ends of wall panels above roof line as required on slopes greater than 1 1/4:12.

**#12-14 X 1 1/4" (12" C.C.)

1"

BL

AP PANELING

Intermediate Girt Detail

STEEL LINE

Eave Height

BL

EAVE STRUT

WALL PANEL

BL

PANEL SIDELAP EAVE STRUT

Sidewall Eave Detail Low side shown. High Side Typical.

** #12-14 X 1 1/4" (12" C.C.) (TYP.)

GIRT

12" (TYP.)

RISE

3" 3"

6"

MIN.

**#12-14 X 1 1/4" (12" C.C.)

WALL PANEL

BL

Panel Endlap Detail

* 1/4-14 X 7/8" (TYP.)

AP PANEL FASTENER INSTALLATION

AP PANEL AT GABLE END

1/4-14 X 7/8" (TYP.) (18" C.C.)

NOTE: · Sidelap holes (7/32" DIA.) must be Pre-drilled in the overlapping corrugation only. · The overlapping corrugation does not have the return leg.

NOTES: ·

Field cut panel if required for corner trim.

· Corner Angle connection/fasteners, refer to Girt Corner Detail.

GIRT

12" (TYP.)

SHEETING SUPPORT (SSP)

TAPE MASTIC CENTERED ON HIGH RIB IS SHOWN THOUGH IS AN ORDER OPTION. REFER TO WALL MASTIC REQUIREMENTS IN ORDERED OPTIONS ON DRAWING COVER PAGE (C1)

1/4-14 X 7/8" (18" C.C.)

** #12-14 X 1 1/4" (12" C.C.) (TYP.)

STEEL LINE

CORNER TRIM (CTA)

RETURN LEG

L

B

* 18" (TYP.)

CORNER ANGLE (A-20)

PRE-DRILL PILOT HOLE IN OVERLAPPING PANEL (SEE NOTE)

12" (TYP.)

AP PANEL 1/4-14 X 7/8" (12" C.C.) (TYP.)

** #12-14 X 1 1/4" (12" C.C.) (TYP.)

2 1/2"

2 1/2"

1 1/2"

BASE MEMBER

TAPE MASTIC AT SIDELAPS, IF ORDERED

B

L

AP PANEL INSTALLATION

AP PANEL SIDE LAPS

AP PANEL STANDARD CORNER CONDITION

CS Wall Details

CS WALL PANEL - The details shown below are typical Chief metal building details. Not all details may apply. Specific details for additional features will be provided for complete installation instructions.

6"

3"

NOTES: · The structural system must be plumb and square prior to panel installation. · Care must be taken to insure panel modularity due to accessory locations and trim. · Insulation has not been shown for clarity. · Blanket insulation must be trimmed above the bottom of panel to prevent water from "WICKING" into the insulation. · Provide air gap of 1/4” min. at bottom of panel to avoid corrosion. · #12-14 X 1 1/4" Fastener spacing is (12" C.C.) unless otherwise noted. ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness ** #12-14 X 2", Blanket Insulation >4" thickness · When possible, CHIEF recommends installing panel so that panel lap is away from prevailing weather.

Top of wall panel is held down 1" from eave height. (Except MSC 2" offset clip, the dimension is 0")

STEEL LINE

GIRT

Clip offset

WALL PANEL

RAKE ANGLE

TAPE MASTIC AT SIDELAPS, IF ORDERED ** #12-14 X 1 1/4 (6" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

TOP OF PURLIN

NOTE: Field cut ends of wall panels above roof line as required on slopes greater than 1 1/4:12.

**#12-14 X 1 1/4" (6" C.C.)

1"

BL

CS PANELING

Intermediate Girt Detail

STEEL LINE

Eave Height

EAVE STRUT

WALL PANEL

BL

PANEL SIDELAP EAVE STRUT

Sidewall Eave Detail Low side shown. High Side Typical.

GIRT

6" (TYP.)

3"

** #12-14 X 1 1/4" (6" C.C.) (TYP.)

RISE

3" 3"

6"

MIN.

**#12-14 X 1 1/4" (6" C.C.)

WALL PANEL

BL

1/4-14 X 7/8" (TYP.) (18" C.C.)

Panel Endlap Detail

* 1/4-14 X 7/8" (TYP.)

CS PANEL FASTENER INSTALLATION

CS PANEL AT GABLE END

NOTE: · Sidelap holes (7/32" DIA.) must be Pre-drilled in the overlapping corrugation only. · The overlapping corrugation does not have the return leg.

NOTES: ·

Field cut panel if required for corner trim.

· Corner Angle connection/fasteners, refer to Girt Corner Detail. · Connection of panel to structure at corner is by the corner trim fasteners.

GIRT

12" (TYP.)

** #12-14 X 1 1/4" (12" C.C.) (TYP.)

1/4-14 X 7/8" (18" C.C.)

CORNER TRIM (CT)

STEEL LINE

CORNER ANGLE (A-20)

RETURN LEG

PRE-DRILL PILOT HOLE IN OVERLAPPING PANEL (SEE NOTE)

* 18" (TYP.)

L

B

TAPE MASTIC CENTERED ON HIGH RIB IS SHOWN THOUGH IS AN ORDER OPTION. REFER TO WALL MASTIC REQUIREMENTS IN ORDERED OPTIONS ON DRAWING COVER PAGE (C1)

6" (TYP.)

3"

CS PANEL

* 1/4-14 X 7/8" (TYP.)

** #12-14 X 1 1/4" (6" C.C.) (TYP.)

2 1/2"

1 1/2"

#12-14 X 1 1/4 (12" C.C.) (TYP.)

BASE MEMBER

B

L

CS PANEL INSTALLATION

CS PANEL SIDE LAPS

CS PANEL STANDARD CORNER CONDITION

AP Panel Openings

AP Panel Openings

AP Metal Bldg Walkdoor-KD-Others

AP Panel - Metal Building Walkdoor -- Knocked-Down (by Chief) or Door Not by Chief Refer to Order Documents for Doors by Chief

Installation Steps: 1. Install Wrap Plate. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Door. 4. Sheeting Support (SSP) 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.

Head Trim (HTT) lapped 4 1/4" min. past edge of door frame. Flush with end of Jamb Trim (JTA).

INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)

2 1/4" X 1/4" PANEL NOTCH

HEADER TRIM (HTT)

2" PANEL SLIT

SHEETING SUPPORT (SSP)

· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)

2" SLIT

2 1/4" X 1/4" NOTCH

WALL PANEL

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

JAMB TRIM (JTA)

DOOR JAMB

DOOR FRAME

EDGE OF DOOR FRAME FLAT OF HEAD TRIM

JAMB TRIM (JTA)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

WALL PANEL

#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)

BL

OPENING WIDTH

**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

ZEE GIRT

JAMB

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)

NOMINAL DOOR OPENING

**#12-14 X 1 1/4" (12" C.C.)

* 1 4 "

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)

DOOR FRAME

BL

1

2 " MIN.

CUT RIB AS NEEDED

SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)

***1/8"-3/4"

DOOR FRAME

OPENING HEIGHT

NOMINAL

DOOR OPENING

*** Locate JTA/SSP trim to cover door frame avoiding interference with latch, door and hinges.

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

JAMB TRIM (JTA)

CEE HEADER

WALKDOOR HEADER TRIM DETAILS

WALKDOOR JAMB TRIM DETAILS

AP Metal Bldg Walkdoor-PA-SF

AP Panel- Metal Building Walkdoor - Pre-Assembled (by Chief) or Self-Framing Not by Chief Refer to Order Documents for Doors Supplied by Chief

Installation Steps: 1. Install Wrap Plate. 2. Door. 3. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Sheeting Support (SSP) 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.

Head Trim (HTT) lapped 4 1/4" min. past edge of door frame. Flush with end of Jamb Trim (JTA).

INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)

2 1/4" X 1/4" PANEL NOTCH

HEADER TRIM (HTT)

2" PANEL SLIT

SHEETING SUPPORT (SSP)

· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)

2" SLIT

WALL PANEL

2 1/4" X 1/4" NOTCH

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

JAMB TRIM (JTA)

DOOR JAMB

DOOR FRAME

EDGE OF DOOR FRAME FLAT OF HEAD TRIM

JAMB TRIM (JTA)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.)

WALL PANEL

#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)

BL

OPENING WIDTH

**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

ZEE GIRT

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)

DOOR SUB FRAME

NOMINAL DOOR OPENING

**#12-14 X 1 1/4" (12" C.C.)

* 1 4 "

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)

DOOR FRAME

BL

1

2 " MIN.

CUT RIB AS NEEDED

SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)

***1/8"-3/4"

DOOR FRAME

OPENING HEIGHT

NOMINAL

DOOR OPENING

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

*** Locate JTA/SSP trim to cover door frame avoiding interference with latch, door and hinges.

JAMB TRIM (JTA)

CEE HEADER

WALKDOOR HEADER TRIM DETAILS

WALKDOOR JAMB TRIM DETAILS

AP OHD or 3-Sided Opening

AP Panel - OHD or 3-Sided Opening

Installation Steps: 1. Door Trim (DT), if applicable. 2. Sheeting Support (SSP) 3. Header Trim (HTT). 4. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets.

INSIDE CLOSURE

Head Trim (HTT) lapped 4 1/4" min. past edge of door jamb. Flush with end of Jamb Trim (JTA).

Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP)

· Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

2" PANEL SLIT

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF)

WALL PANEL

2" X 1/4" NOTCH

2" SLIT

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

DOOR JAMB JAMB TRIM (JTA)

DOOR TRIM (DT)

EDGE OF DOOR JAMB FLAT OF HEAD TRIM

JAMB TRIM (JTA)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS 1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.)

WALL PANEL

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (12" C.C.) INSIDE CLOSURE

JAMB

**#12-14 X 1 1/4" (12" C.C.)

HEADER

2 1/4"

HEADER TRIM (HTT)

* 1 4 "

BL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)

DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

SHEETING SUPPORT (SSP) WALL PANEL 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

OPENING HEIGHT

JAMB TRIM (JTA)

WALKDOOR HEADER TRIM DETAILS

WALKDOOR JAMB TRIM DETAILS

AP Window by Chief

AP Panel - Window by Chief

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Window 5. Sill Jamb Trim (JT), slit and fold up at jamb. 6. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA) Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).

INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP)

2" PANEL SLIT

WALL PANEL

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)

JAMB TRIM (JTA)

LINER COVER TRIMS

2" SLIT

2" X 1/4" NOTCH

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

Optional urethane caulk at JT end. (NOT BY CHIEF)

4 1/4" TO EDGE OF WINDOW JAMB

Optional urethane caulk behind JT (NOT BY CHIEF)

SILL JAMB TRIM (JT) NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL

JAMB TRIM (JTA)

FLAT OF

EDGE OF JAMB HEAD TRIM

Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

LINER COVER TRIM (LCT1)

**#12-14 X 1 1/4" (12" C.C.)

CEE HEADER

INSIDE CLOSURE

2 1 4 "

* 1 4 "

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

HEADER TRIM (HTT) WINDOW BY CHIEF URETHANE CAULK (NOT BY CHIEF)

LINER COVER TRIM (LCT2)

JAMB

LINER COVER TRIM (LCT1)

SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT) * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

OPENING

URETHANE CAULK (NOT BY CHIEF) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY)

WALL PANEL

SILL JAMB TRIM (JT) URETHANE CAULK (NOT BY CHIEF)

JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)

GIRT/SILL

Optional urethane caulk behind JT (NOT BY CHIEF)

SHEETING SUPPORT (SSP)

1/8" x 3/8" BLIND RIVET (7'-0" C.C.)

WALL PANEL (TYP.)

CHIEF WINDOW HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

AP Window or 4-Sided Opening w Jamb Trim–JT

AP Panel - Window Not by Chief or 4-Sided Opening with Sill Jamb Trim – JT

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 4. Sill Jamb Trim (JT), slit and fold up at jamb. 6. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).

INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL

2" PANEL SLIT

LINER COVER TRIMS

Optional Urethane caulk at JT end. (NOT BY CHIEF)

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)

2" SLIT

2" X 1/4" NOTCH

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

4 1/4" TO EDGE OF WINDOW JAMB

OPTIONAL JAMB TRIM FOLD AT END

SILL JAMB TRIM (JT) Optional urethane caulk behind JT (NOT BY CHIEF)

JAMB TRIM (JTA)

FLAT OF

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL

EDGE OF JAMB HEAD TRIM

Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

LINER COVER TRIM (LCT1)

**#12-14 X 1 1/4" (12" C.C.)

CEE HEADER

INSIDE CLOSURE

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

2 1 4 "

* 1 4 "

1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

LINER COVER TRIM (LCT2)

HEADER TRIM (HTT) WINDOW BY CHIEF

JAMB

LINER COVER TRIM (LCT1)

SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

OPENING

**#12-14 X 1 1/4" (12" C.C.)

WALL PANEL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

SILL JAMB TRIM (JT)

INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)

SHEETING SUPPORT (SSP)

GIRT/SILL

WALL PANEL (TYP.) Optional urethane caulk behind JT (NOT BY CHIEF)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

AP Window or 4-Sided Opening w Sill Flashing–WFS

AP Panel - Window Not by Chief or 4-Sided Opening with Sill Flashing – WFS

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

INSIDE CLOSURE

Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).

Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL

2" PANEL SLIT

LINER COVER TRIMS

FIELD VERIFY WFS OFFSET

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)

2" SLIT

2" X 1/4" NOTCH

Urethane sealant at WFS end (NOT BY CHIEF)

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

4 1/4" TO EDGE OF WINDOW JAMB

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)

JAMB TRIM (JTA)

FLAT OF

EDGE OF JAMB HEAD TRIM

Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

LINER COVER TRIM (LCT1)

INSIDE CLOSURE

CEE HEADER

2 1 4 "

* 1 4 "

1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

1/8" X 3/8" BLIND RIVET (3'-0" C.C.)

LINER COVER TRIM (LCT2)

HEADER TRIM (HTT)

JAMB

LINER COVER TRIM (LCT1)

GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

OPENING

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

WALL PANEL

JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

SHEETING SUPPORT (SSP)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

AP Trim Only 4-Sided Opening w Jamb Trim-JT

AP Panel - Trim Only 4-Sided Opening with Sill Jamb Trim – JT

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Jamb Trim (JT), slit and fold up at jamb. 4. Header Trim (HTT). 5. Sheeting Support (SSP) 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure full width of header and sill. 8. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).

INSIDE CLOSURE Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL

2" PANEL SLIT

Opitonal Urethane caulk at JT end. (NOT BY CHIEF) LINER COVER TRIMS

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)

REDUCE LEG LENGTH

2" SLIT

2" X 1/4" NOTCH

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

4 1/4" TO EDGE OF WINDOW JAMB

OPTIONAL JAMB TRIM FOLD AT END

SILL JAMB TRIM (JT)

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL Optional urethane caulk behind JT (NOT BY CHIEF)

JAMB TRIM (JTA)

FLAT OF

EDGE OF JAMB HEAD TRIM

Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

(Window not Shown)

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

FRAMING (NOT BY CHIEF)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

LINER COVER TRIM (LCT1)

**#12-14 X 1 1/4" (12" C.C.)

FRAMING (NOT BY CHIEF)

INSIDE CLOSURE

2 1 4 "

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

* 1 4 "

1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

LINER COVER TRIM (LCT2)

HEADER TRIM (HTT) WINDOW BY CHIEF

LINER COVER TRIM (LCT1)

SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

OPENING

**#12-14 X 1 1/4" (12" C.C.)

WALL PANEL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

SILL JAMB TRIM (JT)

INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.)

SHEETING SUPPORT (SSP)

FRAMING (NOT BY CHIEF)

Urethane caulk behind JT (NOT BY CHIEF)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

WALL PANEL (TYP.)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

AP Trim Only 4-Sided Opening w Sill Flashing-WFS

AP Panel - Trim Only 4-Sided Opening with Sill Flashing – WFS

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Header Trim (HTT). 7. Sheeting Support (SSP) 8. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure full width of header and sill. 7. Jamb Trim (JTA). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

INSIDE CLOSURE

Head Trim (HTT) lapped 4 1/4" min. past edge of window jamb. Flush with end of Jamb Trim (JTA).

Optional urethane caulk at HTT end. (NOT BY CHIEF)

HEADER TRIM (HTT)

2 1/4" X 1/4" PANEL NOTCH

SHEETING SUPPORT (SSP) JAMB TRIM (JTA) WALL PANEL

2" PANEL SLIT

LINER COVER TRIMS

FIELD VERIFY WFS OFFSET

Optional urethane caulk at panel slit and notch. Caulk under JTA. (NOT BY CHIEF) (TYP.)

2" SLIT

2" X 1/4" NOTCH

Optional urethane sealant at WFS end (NOT BY CHIEF)

For best weathertightness performance, JTA/SSP and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, and/or additional urethane caulking Not By Chief may be required.

4 1/4" TO EDGE OF WINDOW JAMB

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) ** #12-14 X 1 1/4" (12" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)

JAMB TRIM (JTA)

FLAT OF

EDGE OF JAMB HEAD TRIM

Optional Urethane caulk around 2" panel slit and under JTA (NOT BY CHIEF) (TYP.)

END OF JAMB TRIM (JTA)

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

(Window not Shown)

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

FRAMING (NOT BY CHIEF)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

LINER COVER TRIM (LCT1)

FRAMING (NOT BY CHIEF)

INSIDE CLOSURE

2 1 4 "

* 1 4 "

1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.) **#12-14 X 1 1/4" (12" C.C.)

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

1/8" X 3/8" BLIND RIVET (3'-0" C.C.)

LINER COVER TRIM (LCT2)

HEADER TRIM (HTT)

LINER COVER TRIM (LCT1)

GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (12" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

OPENING

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)

**#12-14 X 1 1/4" (12" C.C.)

WALL PANEL

JAMB TRIM (JTA) 1/4-14 X 7/8" (12" C.C.)

CUT RIB AS NEEDED

SHEETING SUPPORT (SSP)

FRAMING (NOT BY CHIEF)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

CS Panel Openings

CS Panel Openings

CS Metal Bldg Walkdoor-KD-Others

CS Panel - Metal Building Walkdoor -- Knocked-Down (by Chief) or Door Not by Chief Refer to Order Documents for Doors by Chief

Installation Steps: 1. Install Wrap Plate. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Door. 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

HEADER TRIM (HTT)

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

1" PANEL SLIT

INSIDE CLOSURE

JAMB TRIM (JT)

For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

1" SLIT

2" X 1/4" NOTCH

2" JAMB TRIM NOTCH

COVER TRIM (COT)

DOOR FRAME

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

TRIM DETAIL AT CORNERS

WALL PANEL SLIT

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

WALL PANEL

#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)

BL

OPENING WIDTH

**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

ZEE GIRT

JAMB

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)

NOMINAL DOOR OPENING

* 1 4 "

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)

DOOR FRAME

BL

JAMB TRIM (JT)

1

2 " MIN.

WALL PANEL

CUT RIB AS NEEDED

***1/8"-3/4"

DOOR FRAME

OPENING HEIGHT

**#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)

NOMINAL

*** Locate JT/COT/HTT trim

DOOR OPENING

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

assembly to cover door frame avoiding interference with latch, door and hinges.

CEE HEADER

WALKDOOR HEADER TRIM DETAILS

WALKDOOR JAMB TRIM DETAILS

CS Metal Bldg Walkdoor-PA-SF

CS Panel- Metal Building Walkdoor - Pre-Assembled (by Chief) or Self-Framing Not by Chief Refer to Order Documents for Doors Supplied by Chief

Installation Steps: 1. Install Wrap Plate. 2. Door. 3. Jamb Trim (JT) with notch at header. 4. Header Trim (HTT). 5. Notch and slit wall panel. 6. Place wall panel over trims with foam inside closure. 7. Cover Trim (COT). 8. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

HEADER TRIM (HTT)

1" PANEL SLIT

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

INSIDE CLOSURE

For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

JAMB TRIM (JT)

1" SLIT

2" X 1/4" NOTCH

2" JAMB TRIM NOTCH

COVER TRIM (COT)

DOOR FRAME

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

WALL PANEL SLIT AND NOTCH (Typical at Sill)

TRIM DETAIL AT CORNERS

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

WALL PANEL

#12-14 X 1" PANCAKE HEAD FASTENER (36" C.C.)

BL

OPENING WIDTH

**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE HEADER TRIM (HTT) 1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

ZEE GIRT

DOOR SUBFRAME

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) TYP. SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL)

NOMINAL DOOR OPENING

* 1 4 "

LINER COVER TRIM (LCT1 OR LCT2) (Field modify as req'd)

DOOR FRAME

BL

JAMB TRIM (JT)

1

2 " MIN.

WALL PANEL

CUT RIB AS NEEDED

***1/8"-3/4"

DOOR FRAME

OPENING HEIGHT

**#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)

NOMINAL

*** Locate JT/COT/HTT trim

DOOR OPENING

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

assembly to cover door frame avoiding interference with latch, door and hinges.

CEE HEADER

WALKDOOR HEADER TRIM DETAILS

WALKDOOR JAMB TRIM DETAILS

CS OHD or 3-Sided Opening

CS Panel - OHD or 3-Sided Opening

Installation Steps: 1. Door Trim (DT), if applicable. 2. Jamb Trim (JT) with notch at header. 3. Header Trim (HTT). 4. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closure. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

Head Trim (HTT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

HEADER TRIM (HTT)

1" PANEL SLIT

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

INSIDE CLOSURE

For best weathertightness performance, JT/COT and Head Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

JAMB TRIM (JT)

1" SLIT

2" X 1/4" NOTCH

2" JAMB TRIM NOTCH

DOOR TRIM (DT) OPTIONAL. REFER TO PANEL DRAWINGS.

COVER TRIM (COT)

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

WALL PANEL SLIT AND NOTCH (Typical at Sill)

TRIM DETAIL AT CORNERS

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)

WALL PANEL

BL

OPENING WIDTH

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (6" C.C.) INSIDE CLOSURE

JAMB

DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS

HEADER

1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

HEADER TRIM (HTT)

* 1 4 "

BL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH DOOR TRIM (DT)

JAMB TRIM (JT)

WALL PANEL **#12-14 X 1 1/4" (12" C.C.) COVER TRIM (COT) 1/8" X 3/8" BLIND RIVET (18" C.C.)

DOOR TRIM (DT) (OPTIONAL) REFER TO PANEL DRAWINGS

CUT RIB AS NEEDED

OPENING HEIGHT

For Walkdoors to avoidinterference with latch, door, or hinges, hold JT/COT/HTT trim assembly back from jamb max 3/4", as necessary

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

HEADER TRIM DETAILS

JAMB TRIM DETAILS

CS Window by Chief

CS Panel - Window by Chief

Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings.

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

3. Window with Bulbtite. 4. Sill Jamb Trim (JT). 5. Jamb Trim (JT) with notch at header. 6. Header Trim (HTT). 7. Notch and slit wall panel. 8. Place wall panel over trims with foam inside closures. 9. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

1" PANEL SLIT

JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)

LINER COVER TRIMS

For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

1" SLIT

2" X 1/4" NOTCH

3" TO FLAT OF JAMB TRIM

2" JAMB TRIM NOTCH

COVER TRIM (COT)

SILL JAMB TRIM (JT)

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

WALL PANEL SLIT (Typical at Sill)

TRIM DETAIL AT CORNERS

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)

BL

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT) 3/16" BULBTITE RIVET (12" C.C.) (SIDE ONLY) JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (6" C.C.)

LINER COVER TRIM (LCT1)

CEE HEADER

INSIDE CLOSURE

OPENING WIDTH

* 1 4 "

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

HEADER TRIM (HTT) WINDOW BY CHIEF URETHANE CAULK (NOT BY CHIEF)

LINER COVER TRIM (LCT2)

LINER COVER TRIM (LCT1)

SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT) * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

**#12-14 X 1 1/4" (12" C.C.) WALL PANEL

OPENING

JAMB TRIM (JT)

CUT RIB AS NEEDED

URETHANE CAULK (NOT BY CHIEF)

1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)

URETHANE CAULK (NOT BY CHIEF)

SILL JAMB TRIM (JT) INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.)

GIRT/SILL

1/8" x 3/8" BLIND RIVET (7'-0" C.C.)

WALL PANEL (TYP.)

CHIEF WINDOW HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

CS Window or 4-Sided Opening w Jamb Trim-JT

CS Panel - Window Not by Chief or 4-Sided Opening with Sill Jamb Trim – JT

Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Jamb Trim (JT). 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closures. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

1" PANEL SLIT

JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)

LINER COVER TRIMS

For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

1" SLIT

2" X 1/4" NOTCH

3" TO FLAT OF JAMB TRIM

2" JAMB TRIM NOTCH

OPTIONAL JAMB TRIM FOLD AT END

COVER TRIM (COT)

SILL JAMB TRIM (JT) NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

WALL PANEL SLIT AND NOTCH (Typical at Sill)

TRIM DETAIL AT CORNERS

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.) **#12-14 X 1 1/4" (6" C.C.)

BL

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

LINER COVER TRIM (LCT1)

INSIDE CLOSURE

CEE HEADER

* 1 4 " * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

OPENING WIDTH

JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

HEADER TRIM (HTT)

LINER COVER TRIM (LCT2)

LINER COVER TRIM (LCT1)

SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

**#12-14 X 1 1/4" (12" C.C.) WALL PANEL

JAMB TRIM (JT)

OPENING

CUT RIB AS NEEDED

1/8" X 3/8" BLIND RIVET, 18" C.C. WITH COVER TRIM (LCT)

1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)

SILL JAMB TRIM (JT) INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.)

GIRT/SILL

1/8" x 3/8" BLIND RIVET (7'-0" C.C.)

WALL PANEL (TYP.)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB

CS Window or 4-Sided Opening w Sill Flashing-WFS

CS Panel - Window Not by Chief or 4-Sided Opening with Sill Flashing – WFS

Header Trim (HTT) and Sill Trim (JT) lapped 3" min. past flat of Jamb Trim (JT). Flush with Cover Trim (COT).

Installation Steps: 1. Install Wrap Plate, if applicable. 2. Liner Cover Trim(LCT), if applicable. Use with Liner/Backer. Refer to Liner or Partition Panel Drawings. 3. Sill Trim Flashing (WFS), slit and fold up at jamb. 4. Jamb Trim (JT) with notch at header. 5. Header Trim (HTT). 6. Notch and slit wall panel. 7. Place wall panel over trims with foam inside closures. 8. Cover Trim (COT). Notes: · Drill Ø1/8" holes for Blind Rivets. · Rivets spaced at 7'-0" C.C. are temporary fasteners. · ** #12-14 X 1-1/4", Blanket Insulation <=4" thickness. · ** #12-14 X 2", Blanket Insulation >4" thickness.

2" JAMB TRIM NOTCH

2" X 1/4" PANEL NOTCH

1" PANEL SLIT

JAMB TRIM (JT) INSIDE CLOSURE HEADER TRIM (HTT)

LINER COVER TRIMS

FIELD VERIFY WFS OFFSET

For best weathertightness performance, JT/COT and Head/Sill Trim assembly should land in flat of panel. Layout, verify, and consider field locating framed opening as necessary. If this condition cannot be achieved, special field trim modifications, omitting COT trim, and/or additional urethane caulking Not By Chief may be required.

1" SLIT

2" X 1/4" NOTCH

3" TO FLAT OF JAMB TRIM

2" JAMB TRIM NOTCH

COVER TRIM (COT)

NOTCH AND SLIT WALL PANEL FOR EXTENSION OF TRIM. (TYP.) **#12-14 X 1 1/4" (6" C.C.) (TYP.) WALL PANEL SILL TRIM FLASHING (WFS) 1/8" X 3/8" BLIND RIVET (12" C.C.)

Optional Urethane caulk around 1" panel slit and under COT (NOT BY CHIEF) (TYP.)

FLAT OF JAMB TRIM FLAT OF HEAD TRIM

WALL PANEL SLIT AND NOTCH (Typical at Sill)

TRIM DETAIL AT CORNERS

(Window not Shown)

ZEE GIRT #12-14 X 1" PANCAKE HEAD (36" C.C.) (TYP.)

BL

1/8" X 3/8" BLIND RIVET, (18" C.C.) WITH LINER COVER TRIM (LCT)

1/8" X 3/8" BLIND RIVET (7'-0" C.C.)

**#12-14 X 1 1/4" (6" C.C.)

LINER COVER TRIM (LCT1)

INSIDE CLOSURE

CEE HEADER

* 1 4 "

* Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.

1/8" X 3/8" BLIND RIVET (3'-0" C.C.)

OPENING WIDTH

JAMB 1/8" X 3/8" BLIND RIVET (7'-0" C.C.) (TYP.)

LINER COVER TRIM (LCT2)

HEADER TRIM (HTT)

LINER COVER TRIM (LCT1)

GIRT/SILL INSIDE CLOSURE **#12-14 X 1 1/4" (6" C.C.) WALL PANEL (TYP.) SILL TRIM FLASHING (WFS) SPECIAL PLATE. REFER TO FRAMING PLANS FOR PIECE MARK (PL) LINER COVER TRIM (LCT2)

BL

**#12-14 X 1 1/4" (12" C.C.) WALL PANEL

JAMB TRIM (JT)

OPENING

1/8" X 3/8" BLIND RIVET (3'-0" C.C.) 1/8" X 3/8" BLIND RIVET (12" C.C.)

CUT RIB AS NEEDED

1/8" X 3/8" BLIND RIVET (18" C.C.) (TYP.) COVER TRIM (COT)

OPENING DETAILS AT HEADER AND SILL

FRAMED OPENING DETAILS AT JAMB