Composite Material, Rigid Board, R-Seal
Composite Material, Rigid Board , R-Seal Sections & Details
All details downloadable in .dwg and .pdf
Table of Contents
Eave Strut I8-18.Eave Strut for STC-MSC-Ridgid Board-ERB-Low Side-Low Pitch J1-51.Eave Strut for STC-MSC-Ridgid Board-Flush-Low Side-Low Pitch J1-52.Eave Strut for STC-MSC-Ridgid Board-Inset-Low Side-Low Pitch J2-26.Eave Strut for STC-MSC-Ridgid Board-Outset-Low Side-Low Pitch CS Eave CS Rigid Roof-Wall Low Side Gutter CS Deck Rigid Roof-Wall Low Side Gutter CS Rigid Roof-Wall High Side CS Deck Rigid Roof-Wall High Side CS Gable CS Rigid Roof-Wall Gable CS Deck Rigid Roof-Wall Gable CS Height Change CS Rigid Roof-Wall High Side Height Change CS Deck Rigid Roof-Wall High Side Height Change CS Rigid Roof-Wall Gable Height Change CS Deck Rigid Roof-Wall Gable Height Change STC-MSC Eave STC-MSC Rigid Roof-Wall Low Side Gutter STC-MSC Deck Rigid Roof-Wall Low Side Gutter STC-MSC Rigid Roof-Wall High Side STC-MSC Deck Rigid Roof-Wall High Side STC-MSC Eave Extension STC-MSC Rigid Roof-Wall Eave Ext Low Side Gutter CS-AP Soffit STC-MSC Rigid Roof-Wall Eave Ext Low Side Gutter CS-AP Soffit w Z STC-MSC Rigid Roof-Wall Eave Ext High Side CS-AP Soffit STC-MSC Rigid Roof-Wall Eave Ext High Side CS-AP Soffit w Z STC-MSC Gable STC-MSC Deck Rigid Roof-Wall Gable Tail STC-MSC Rigid Roof-Wall Gable Field TT STC-MSC Deck Rigid Roof-Wall Gable Field TT STC-MSC Gable Extension STC-MSC Rigid Roof-Wall Gable Ext Lead STC-MSC Height Change STC-MSC Rigid Roof-Wall Gable Height Change Lead STC-MSC Deck Rigid Roof-Wall Gable Height Change Lead STC-MSC Rigid Roof-Wall Gable Lead End STC-MSC Deck Rigid Roof-Wall Gable Lead STC-MSC Rigid Roof-Wall Gable Tail
Table of Contents
STC-MSC Rigid Roof-Wall High Side Height Change STC-MSC Deck Rigid Roof-Wall High Side Height Change STC-MSC Ridge STC-MSC Rigid Roof Ridge STC-MSC Deck Rigid Roof Ridge STC-MSC Splice MSC Rigid Roof Splice Low MSC Deck Rigid Roof Splice Low STC Rigid Roof Panel Splice STC Deck Rigid Roof Panel Splice Low Wall Panel AP-CS
AP Wall Details Rigid Wall CS Wall Details Rigid Wall Wall Panel Base Brittle Material at Panel Rigid Wall AP Panel Openings
AP Metal Bldg Walkdoor-KD-Others Rigid Wall AP Metal Bldg Walkdoor-PA-SF Rigid Wall AP OHD or 3-Sided Opening Rigid Wall AP Window by Chief Rigid Wall
AP Window or 4-Sided Opening w Jamb Trim-JT Rigid Wall AP Window or 4-Sided Opening w Sill Flashing-WFS Rigid Wall CS Panel Openings
CS Metal Bldg Walkdoor-KD-Others Rigid Wall CS Metal Bldg Walkdoor-PA-SF Rigid Wall CS OHD or 3-Sided Opening Rigid Wall CS Window by Chief Rigid Wall
CS Window or 4-Sided Opening w Jamb Trim-JT Rigid Wall CS Window or 4-Sided Opening w Sill Flashing-WFS Rigid Wall R-Seal Splice R-Seal Splice at Purlin R-Seal Splice at Girt
EaveStrut
EaveStrut
I8-18.Eave Strut for STC-MSC-Ridgid Board-ERB-Low Side-Low Pitch
DRAFTING NOTE: 3/8" is for STC-MSC LOW Clip option ONLY
Top of Eave Angle to be installed 3/8" above top of insulation.
BL
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.) EAVE ANGLE (PL-x)
TOP OF INSULATION
TOP OF PURLINS
EAVE HEIGHT
EAVE STRUT
(2) 5/8" X 1 1/2" BOLTS w/ HARD WASHERS AT C-SECTION SIDE ENDWALL RAFTER BEAM
Special Roof Panel Modify Section as Required
EAVE STRUT TO ENDWALL RAFTER BEAM STANDING SEAM ROOF
I8
J1-51.Eave Strut for STC-MSC-Ridgid Board-Flush-Low Side-Low Pitch
DRAFTING NOTE: 3/8" is for STC-MSC LOW Clip option ONLY
Top of Eave Angle to be installed 3/8" above top of insulation.
BL
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.) EAVE ANGLE (PL-x)
TOP OF INSULATION
TOP OF PURLINS
EAVE HEIGHT
EAVE STRUT
(4) 5/8" X 1 1/2" BOLTS w/ HARD WASHERS AT C-SECTION SIDE FRAME COLUMN
Special Roof Panel Modify Section as Required
EAVE STRUT TO RIGID FRAME STANDING SEAM ROOF
J1
J1-52.Eave Strut for STC-MSC-Ridgid Board-Inset-Low Side-Low Pitch
DRAFTING NOTE: 3/8" is for STC-MSC LOW Clip option ONLY
Top of Eave Angle to be installed 3/8" above top of insulation.
BL
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.) EAVE ANGLE (PL-x)
TOP OF INSULATION
TOP OF PURLINS
EAVE HEIGHT
EAVE STRUT
(4) 5/8" X 1 1/2" BOLTS w/ HARD WASHERS AT C-SECTION SIDE FRAME COLUMN
Special Roof Panel Modify Section as Required
EAVE STRUT TO RIGID FRAME STANDING SEAM ROOF
J1
J2-26.Eave Strut for STC-MSC-Ridgid Board-Outset-Low Side-Low Pitch
DRAFTING NOTE: 3/8" is for STC-MSC LOW Clip option ONLY
Top of Eave Angle to be installed 3/8" above top of insulation.
BL
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.) EAVE ANGLE (PL-x)
TOP OF INSULATION
TOP OF PURLINS
EAVE HEIGHT
EAVE STRUT
(4) 5/8" X 1 1/2" BOLTS w/ HARD WASHERS AT C-SECTION SIDE FRAME COLUMN
EAVE STRUT TO RIGID FRAME STANDING SEAM ROOF Special Roof Panel Modify Section as Required
J2
CSEave
CSEave
CS Rigid Roof-Wall Low Side Gutter
NOTES: * Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
1/4-14 X 7/8" WT (6" C.C.)
INSDIE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM GUTTER STRAP (GS) (_____ C.C.)
BL
INSIDE CLOSURE (2) 1/4-14 X 7/8" WT CS ROOF PANEL
GUTTER STRAP LAP 8 11 16 "
(1) 1/4-14 X 7/8" (TRIM COLOR)
4"
PANEL OVERHANG FROM INSUL.
TOP OF PURLIN
DRAFTING NOTE: Include Corresponding Standard Details. - CS Panel Details - UL90 - Panel Splice.
1"
* _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) (2) #12-14 X _____" (1 EACH SIDE OF HI-RIB) #12-14 X _____" (6" C.C.)
EAVE
HEIGHT
EAVE GUTTER (EGA) 1/4-14 X 7/8" (12" C.C.)
EAVE STRUT
TRIM CAP (TCM)
#12-14 X _____" (6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
WALL PANEL INSIDE CLOSURE
* _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
CS Deck Rigid Roof-Wall Low Side Gutter
NOTES: * Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. ** See Roof Deck Fastener Details for additional fastener spacing information.
1/4-14 X 7/8" WT (6" C.C.)
INSDIE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM GUTTER STRAP (GS) (_____ C.C.)
BL
INSIDE CLOSURE (2) 1/4-14 X 7/8" WT
8 11
16 "
GUTTER STRAP LAP
(1) 1/4-14 X 7/8" (TRIM COLOR)
4"
CS ROOF PANEL
PANEL OVERHANG FROM INSUL.
EAVE GUTTER (EGA)
TOP OF PURLIN
1"
DECKING
DRAFTING NOTE: Include Corresponding Standard Details. - CS Panel Details - UL90 - Panel Splice.
* _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) (2) #12-14 X _____" (1 EACH SIDE OF HI-RIB) #12-14 X _____" (6" C.C.) ** ___ X ___ (___" C.C.)
EAVE
HEIGHT
1/4-14 X 7/8" (12" C.C.) TRIM CAP (TCM)
INSIDE CLOSURE
EAVE STRUT
#12-14 X _____" (6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
* _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
WALL PANEL
CS Rigid Roof-Wall High Side
NOTES: * See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM". ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
CS ROOF PANEL
1/4-14 X 7/8" WT (12" C.C.)
TAPE MASTIC ON TOP OF CLOSURE
HIGHSIDE EAVE TRIM (HSEC)
1/4-14 X 7/8" WT (12" C.C.)
TAPE MASTIC AT PANEL LAP
#12-14 X ___" (6" C.C.)
BL
1 1
* OUTSIDE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM
2 "
INSIDE CLOSURE
PANEL OVERHANG FROM INSUL.
1/4-14 X 7/8" (12" C.C.) HI-SIDE EAVE TRIM (HSEC)
CS ROOF PANEL
WALL PANEL
CS INSIDE CLOSURE
CS OUTSIDE CLOSURE
1"
TOP OF PURLIN
TAPE MASTIC ON BOTTOM OF CLOSURE
EAVE STRUT ** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
EAVE
HEIGHT
SPECIAL TRIM CAP (SPT-x)
PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)
#12-14 X ___" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
INSIDE CLOSURE
EAVE MEMBER
OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.)
TRIM CAP (TCH)
WALL PANEL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM ≤ 2:12
(Rigid Insulation Not Shown)
CS Deck Rigid Roof-Wall High Side
NOTES: * See isometric detail "PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM". ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. *** See Roof Deck Fastener Details for additional fastener spacing information.
CS ROOF PANEL
1/4-14 X 7/8" WT (12" C.C.)
TAPE MASTIC ON TOP OF CLOSURE
HIGHSIDE EAVE TRIM (HSEC)
#12-14 X ___" (6" C.C.) 1/4-14 X 7/8" WT (12" C.C.)
TAPE MASTIC AT PANEL LAP
BL
1 1
* OUTSIDE CLOSURE w/ TAPE MASTIC TOP AND BOTTOM
2 "
INSIDE CLOSURE
PANEL OVERHANG FROM INSUL.
SPECIAL TRIM CAP (SPT-x) 1/4-14 X 7/8" (12" C.C.) HI-SIDE EAVE TRIM (HSEC)
CS ROOF PANEL
WALL PANEL
1"
CS INSIDE CLOSURE
CS OUTSIDE CLOSURE
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) TOP OF PURLIN
TAPE MASTIC ON BOTTOM OF CLOSURE
EAVE
HEIGHT
DECKING
OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.)
EAVE STRUT
PIGTAIL TAPE MASTIC (Install a "Pig Tail" down the bearing leg of panel to form a continuous line of tape mastic with panel lap and closure.)
#12-14 X ___" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) *** ___ X ___ (___" C.C.)
WALL PANEL INSIDE CLOSURE
EAVE MEMBER
TRIM CAP (TCH)
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
PIGTAIL TAPE MASTIC INSTALLATION WITH HIGH SIDE EAVE TRIM ≤ 2:12
(Rigid Insulation and Deck Not Shown)
CSGable
CSGable
CS Rigid Roof-Wall Gable
NOTES: * Field cut outside closure for higher roof pitches.
** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
#12-14 X _____" (12" C.C.) DOUBLE BEAD TAPE MASTIC CS ROOF PANEL ** ____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
BL
RAKE ANGLE (A-20) GABLE TRIM (SPT-x) #12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
2 1/8"
INSIDE CLOSURE
1/4-14 X 7/8" (12" C.C.) *OUTSIDE CLOSURE
WALL PANEL ** _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
PURLIN
CS Deck Rigid Roof-Wall Gable
NOTES: * Field cut outside closure for higher roof pitches.
** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
***See Roof Deck Fastener Details for additional fastener spacing information.
#12-14 X _____" (12" C.C.)
BL
DOUBLE BEAD TAPE MASTIC CS ROOF PANEL ** ____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
RAKE ANGLE (A-20) GABLE TRIM (SPT-x) #12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
2 1/8"
INSIDE CLOSURE
1/4-14 X 7/8" (12" C.C.) * OUTSIDE CLOSURE
DECKING
WALL PANEL ** _____" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** ___ X ___ (2 EACH PURLIN)
PURLIN
CS Height Change
CS Height Change
CS Rigid Roof-Wall High Side Height Change
NOTES: * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
BL
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE WALL PANEL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (48" C.C.)
1/4-14 X 7/8" WT (12" C.C.) HEIGHT CHANGE TRIM (LHTC)
HEIGHT CHANGE GIRT
2 ROWS DOUBLE BEAD MASTIC TOP & BOTTOM OF OUTSIDE CLOSURE
DRAFTING NOTE: Include Corresponding Standard Details. - Height Change Isometric
CS ROOF PANEL #12-14 X _____" (6" C.C.) OUTSIDE CLOSURE (2" X 3')
* 1 4 "
3 3/4"
x"
1 1
2 "
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
INSULATION TO PANEL
SPECIAL TRIM (SPT-x) (PW)
9"
#12-14 X 1" PANCAKE HEAD (48" C.C.)
PURLIN
CS Deck Rigid Roof-Wall High Side Height Change
NOTES: * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. ***See Roof Deck Fastener Details for additional fastener spacing information.
BL
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE WALL PANEL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (48" C.C.)
1/4-14 X 7/8" WT (12" C.C.) HEIGHT CHANGE TRIM (LHTC)
DRAFTING NOTE: Include Corresponding Standard Details. - Height Change Isometric
HEIGHT CHANGE GIRT
2 ROWS DOUBLE BEAD MASTIC TOP & BOTTOM OF OUTSIDE CLOSURE
CS ROOF PANEL #12-14 X _____" (6" C.C.) OUTSIDE CLOSURE (2" X 3')
* 1 4 "
3 3/4"
x"
**** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) DECKING
1 1
2 "
SPECIAL TRIM (SPT-x) (PW)
INSULATION TO PANEL
9"
#12-14 X 1" PANCAKE HEAD (48" C.C.)
*** ___ X ___ (___" C.C.)
PURLIN
CS Rigid Roof-Wall Gable Height Change
NOTES: * Field cut bottom of wall panels to match roof slope. Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
BL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
* WALL PANEL
HEIGHT CHANGE ANGLE (PL-x) #12-14 X ____"
DOUBLE BEAD TAPE MASTIC CS ROOF PANEL #12-14 X _____" (12" C.C.) HEIGHT CHANGE TRIM (RHT) INSIDE CLOSURE
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
* 1 4 "
**___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
CS Deck Rigid Roof-Wall Gable Height Change
NOTES: * Field cut bottom of wall panels to match roof slope. Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
***See Roof Deck Fastener Details for additional fastener spacing information.
BL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
* WALL PANEL
DOUBLE BEAD TAPE MASTIC CS ROOF PANEL #12-14 X _____" (12" C.C.) HEIGHT CHANGE TRIM (RHT) INSIDE CLOSURE
HEIGHT CHANGE ANGLE (PL-x) #12-14 X ____"
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
* 1 4 "
DECKING
**___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** ___ X ___ (2 EACH PURLIN)
STC-MSC Eave
STC-MSC Eave
STC-MSC Rigid Roof-Wall Low Side Gutter
NOTES: * Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 X 7/8" WT's between gutter strap and roof panel. ** See Isometric Trapezoid Plug Installation detail for installation instructions. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE *(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)
1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) **TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) GUTTER STRAP (GSM) AT EACH PANEL HI-RIB
BL
x"
GUTTER STRAP LAP
4 1
2 "
PANEL OVERHANG FROM INSUL.
#12-14 X 1 1/4" (TRIM COLOR)
Top of Eave Angle to be installed 3/8" above top of insulation.
EAVE GUTTER (EGM)
TOP OF PURLIN
TOP OF INSULATION
EAVE ANGLE
1"
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
TOP OF PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
EAVE STRUT
EAVE
EAVE STRUT
HEIGHT
1/4-14 X 7/8" (12" C.C.) TRIM CAP (TCM)
EAVE ANGLE (PL-x)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) (2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
INSIDE CLOSURE
EAVE ANGLE CONNECTION DRAFTING NOTE: 3/8" is for MSC/STC LOW Clip option ONLY.
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Eave Isometric
WALL PANEL
STC-MSC Deck Rigid Roof-Wall Low Side Gutter
NOTES: * Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 X 7/8" WT's between gutter strap and roof panel. ** See Isometric Trapezoid Plug Installation detail for installation instructions. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
1/4-14 X 7/8" WT (6" C.C.) **TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) GUTTER STRAP (GSM) AT EACH PANEL HI-RIB
STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE *(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)
BL
x"
GUTTER STRAP LAP
4 1
2 "
PANEL OVERHANG FROM INSUL.
#12-14 X 1 1/4" (TRIM COLOR)
Top of Eave Angle to be installed 3/8" above top of insulation.
EAVE GUTTER (EGM)
TOP OF INSULATION
EAVE ANGLE
TOP OF PURLIN *** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1"
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
TOP OF PURLIN
EAVE STRUT
DECKING
EAVE
EAVE STRUT
HEIGHT
**** ___ X ___ (___" C.C.)
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.) TRIM CAP (TCM) INSIDE CLOSURE
EAVE ANGLE (PL-x)
EAVE ANGLE CONNECTION DRAFTING NOTE: 3/8" is for MSC/STC LOW Clip option ONLY.
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) (2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Eave Isometric
WALL PANEL
STC-MSC Rigid Roof-Wall High Side
NOTES: * For screw spacing refer to High Eave Trim detail in the STC/MSC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" STC/MSC - Tri-Bead Tape Mastic from roll. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
**TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE
TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT
BL
PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) BEARING PLATE (HW7500)
2 3 4 " PANEL OVERHANG FROM INSUL.
BACK-UP PLATE
HI-SIDE EAVE TRIM (HSEMC)
INSIDE CLOSURE
STC/MSC ROOF PANEL
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
TOP OF PURLIN
1"
EAVE STRUT *** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
EAVE
HEIGHT
1/4-14 X 7/8" (12" C.C.) 1/4-14 X 7/8" (12" C.C.)
JAMB TRIM
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
OUTSIDE CLOSURE
WALL PANEL
STC-MSC Deck Rigid Roof-Wall High Side
NOTES: * For screw spacing refer to High Eave Trim detail in the STC/MSC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" STC/MSC - Tri-Bead Tape Mastic from roll. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT
BACK-UP PLATE **TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE
BL
PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) BEARING PLATE (HW7500)
2 3 4 " PANEL OVERHANG FROM INSUL.
HI-SIDE EAVE TRIM (HSEMC)
OUTSIDE CLOSURE
STC/MSC ROOF PANEL
1"
TOP OF PURLIN
DECKING
EAVE STRUT *** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) **** ___ X ___ (___" C.C.)
EAVE
HEIGHT
1/4-14 X 7/8" (12" C.C.) 1/4-14 X 7/8" (12" C.C.)
JAMB TRIM
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
INSIDE CLOSURE
WALL PANEL
STC-MSC Eave Extension
STC-MSC Eave Extension
STC-MSC Rigid Roof-Wall Eave Ext Low Side Gutter CS-AP Soffit
NOTES: *
See Isometric Trapezoid Plug Installation detail for installation instructions. ** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 X 7/8" WT's between gutter strap and roof panel. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
Top of Eave Angle to be installed 3/8" above top of insulation.
TOP OF INSULATION
EAVE ANGLE
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
TOP OF PURLIN
EAVE STRUT
EAVE ANGLE CONNECTION DRAFTING NOTE: 3/8" is for MSC/STC LOW Clip option ONLY.
DRAFTING NOTES: If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer.
PANEL OVERHANG
GUTTER STRAP LAP
PITCH
<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12 ALL DIMENSIONS IN INCHES 4 1/2 3 1/2 3 1/2 4 4 1/4
7 7/8 7 1/2
7 1/8
BL
6 7/16
PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION (NOT BY CHIEF) PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
5 3/4
1/4-14 X 1 1/4" WT (8 PER PANEL)
** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL
SPECIAL PLATE (PL-x) (2) 1/4-14 X 1" (2'-0" C.C.)
METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS
x"
1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) *TRAPEZOID PLUG (TRP) AT EACH HIGH RIB GUTTER STRAP (GSM) AT PANEL HI-RIBS #12-14 X 1 1/4" (TRIM COLOR)
GUTTER STRAP LAP
x"
STC/MSC ROOF PANEL 1/4-14 X 1 1/4" WT (6 PER PANEL)
PANEL OVERHANG FROM EXT. PURLIN
TOP OF PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
EAVE GUTTER (EGM)
1"
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) **** EAVE ANGLE (PL-x)
INTERMED. PURLIN
#12-14 X 1 14" (12" C.C.) (TRIM COLOR)
EAVE HEIGHT
EXTENSION FLASHING (SPT-x) EAVE EXTENSION FLASHING (EEFA) 1/4-14 X 7/8" (12" C.C.)
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) WALL PANEL OUTSIDE CLOSURE INSIDE CLOSURE
SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)
1/4-14 X 7/8" (12" C.C.)
#12-14 X 1 1/4" (12" C.C.)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
OUTSIDE CLOSURE
SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.)
STC-MSC Rigid Roof-Wall Eave Ext Low Side Gutter CS-AP Soffit wZ
NOTES: *
See Isometric Trapezoid Plug Installation detail for installation instructions. ** Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 X 7/8" WT's between gutter strap and roof panel. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
Top of Eave Angle to be installed 3/8" above top of insulation.
TOP OF INSULATION
EAVE ANGLE
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
TOP OF PURLIN
EAVE STRUT
EAVE ANGLE CONNECTION DRAFTING NOTE: 3/8" is for MSC/STC LOW Clip option ONLY.
PANEL OVERHANG
GUTTER STRAP LAP
PITCH
<=3/4:12 >3/4:12 to <=1 1/2:12 >1 1/2:12 to <=2 1/2:12 >2 1/2:12 to <=3 1/2:12 >3 1/2:12 to <=4 1/2:12 ALL DIMENSIONS IN INCHES 4 1/2 3 1/2 3 1/2 4 4 1/4
7 7/8 7 1/2
DRAFTING NOTES: If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer. PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
7 1/8
BL
6 7/16
5 3/4
PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION (NOT BY CHIEF)
1/4-14 X 1 1/4" WT (8 PER PANEL)
** (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL
STC/MSC ROOF PANEL SPECIAL PLATE (PL-x) (2) 1/4-14 X 1" (2'-0" C.C.)
METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS
x"
1/4-14 X 7/8" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) *TRAPEZOID PLUG (TRP) AT EACH HIGH RIB GUTTER STRAP (GSM) AT PANEL HI-RIBS #12-14 X 1 1/4" (TRIM COLOR)
GUTTER STRAP LAP
x"
1/4-14 X 1 1/4" WT (6 PER PANEL)
PANEL OVERHANG FROM EXT. PURLIN
TOP OF PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
EAVE GUTTER (EGM)
1"
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) EAVE ANGLE (PL-x)
INTERMED. PURLIN
#12-14 X 1 14" (12" C.C.) (TRIM COLOR)
EAVE HEIGHT
EXTENSION FLASHING (SPT-x) EAVE EXTENSION FLASHING (EEFA) 1/4-14 X 7/8" (12" C.C.)
(2) #12-14 X 1" PANCAKE HEAD (2'-0" C.C.)
(2) 1/4-14 X 1" (2'-0" C.C.)
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) WALL PANEL OUTSIDE CLOSURE INSIDE CLOSURE
#12-14 X 1 1/4" (12" C.C.) SPECIAL ANGLE (PL-x) SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)
1/4-14 X 7/8" (12" C.C.)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Eave Isometric
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
OUTSIDE CLOSURE
SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.)
STC-MSC Rigid Roof-Wall Eave Ext High Side CS-AP Soffit
NOTES: * For screw spacing refer to High Eave Trim detail in the STC/MSC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" STC/MSC - Tri-Bead Tape Mastic from roll.. ***Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
DRAFTING NOTES: If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer.
*1/4-14 X 7/8" WT TRI-BEAD TAPE MASTIC
1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE
PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION
BL
PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) (TYP.)
3 1
2 "
(NOT BY CHIEF)
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
PANEL OVERHANG FROM EXT. PURLIN
STC/MSC ROOF PANEL SPECIAL PLATE (PL-x)
**TRI-BEAD TAPE MASTIC
BACK-UP PLATE
PRE-GLUED THERMAL SPACER (NOT BY CHIEF) BEARING PLATE (HW7500)
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)
TOP OF PURLIN
HI-SIDE EAVE TRIM (HSEMC)
INTERMED. PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1"
1/4-14 X 7/8" (12" C.C.) HIGH SIDE EXTENSION FLASHING (SPT-x)
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE
EAVE HEIGHT
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1/4-14 X 7/8" (12" C.C.)
SOFFIT PANEL
SOFFIT TRIM (ESTA) 1/4-14 X 7/8" (12" C.C.) WALL PANEL OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)
#12-14 X 1 1/4" (12" C.C.)
OUTSIDE CLOSURE
STC-MSC Rigid Roof-Wall Eave Ext High Side CS-AP Soffit w Z
NOTES: * For screw spacing refer to High Eave Trim detail in the STC/MSC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" STC/MSC - Tri-Bead Tape Mastic from roll.. ***Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
DRAFTING NOTES: If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer.
*1/4-14 X 7/8" WT TRI-BEAD TAPE MASTIC
1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE
PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION
BL
PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN) (TYP.)
3 1
2 "
(NOT BY CHIEF)
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
PANEL OVERHANG FROM EXT. PURLIN
STC/MSC ROOF PANEL SPECIAL PLATE (PL-x)
**TRI-BEAD TAPE MASTIC
BACK-UP PLATE
PRE-GLUED THERMAL SPACER (NOT BY CHIEF) BEARING PLATE (HW7500)
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)
TOP OF PURLIN
HI-SIDE EAVE TRIM (HSEMC)
INTERMED. PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1"
1/4-14 X 7/8" (12" C.C.) HIGH SIDE EXTENSION FLASHING (SPT-x)
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE
EAVE HEIGHT
(2) 1/4-14 X 1" (2'-0" C.C.) SPECIAL ANGLE (PL-x) (TYP.)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1/4-14 X 7/8" (12" C.C.)
SOFFIT PANEL
SOFFIT TRIM (ESTA) 1/4-14 X 7/8" (12" C.C.) WALL PANEL OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)
#12-14 X 1 1/4" (12" C.C.)
OUTSIDE CLOSURE
STC-MSC Gable
STC-MSC Gable
STC-MSC Rigid Roof-Wall Gable Lead End
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
1/4-14 X 1 1/4" WT (12" C.C.) TRI-BEAD TAPE SEALER *1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER (NOT BY CHIEF) 1/4-14 X ____" W/O (2 EACH PURLIN)
RAKE SUPPORT (A-20-S) GABLE TRIM (SPT-x)
BL
ROOF PANEL SUPPORT (A-20-L)
(2) 1/4-14 X 7/8"
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
INSIDE CLOSURE
**OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
RAKE ANGLE (A-20-B)
PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
STC-MSC Deck Rigid Roof-Wall Gable Lead
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
TRI-BEAD TAPE MASTIC
1/4-14 X 1 1/2" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * PRE-GLUED THERMAL SPACER (NOT BY CHIEF) 1/4-14 X ____" W/O (2 EACH PURLIN)
GABLE TRIM (SPT-x) RAKE SUPPORT (A-20-S) ROOF PANEL SUPPORT ANGLE (A-20-L)
BL
(2) 1/4-14 X 7/8"
STC/MSC ROOF PANEL *** ____" RIGID BOARD INSULATION (NOT BY CHIEF)
INSIDE CLOSURE
#12-14 X _____" (6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE
DECKING
PURLIN
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) **** ___ X ___ (2 EACH PURLIN)
*** _____" RIGID BOARD INSULATION (NOT BY CHIEF)
RAKE ANGLE (A-20)
STC-MSC Rigid Roof-Wall Gable Tail
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
1/4-14 X 1 1/4" WT (12" C.C.) TRI-BEAD TAPE SEALER *1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER (NOT BY CHIEF) 1/4-14 X ____" W/O (2 EACH PURLIN)
RAKE SUPPORT (A-20-S) GABLE TRIM (SPT-x)
BL
ROOF PANEL SUPPORT (A-20-L)
(2) 1/4-14 X 7/8"
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
INSIDE CLOSURE
**OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
RAKE ANGLE (A-20-B)
PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
STC-MSC Deck Rigid Roof-Wall Gable Tail
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
TRI-BEAD TAPE MASTIC
1/4-14 X 1 1/2" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * PRE-GLUED THERMAL SPACER (NOT BY CHIEF) 1/4-14 X ____" W/O (2 EACH PURLIN)
GABLE TRIM (SPT-x) RAKE SUPPORT (A-20-S) ROOF PANEL SUPPORT ANGLE (A-20-L)
BL
(2) 1/4-14 X 7/8"
STC/MSC ROOF PANEL *** ____" RIGID BOARD INSULATION (NOT BY CHIEF)
INSIDE CLOSURE
#12-14 X _____" (6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE
DECKING
PURLIN
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) **** ___ X ___ (2 EACH PURLIN)
*** _____" RIGID BOARD INSULATION (NOT BY CHIEF)
RAKE ANGLE (A-20)
STC-MSC Rigid Roof-Wall Gable Field TT
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
RAKE SUPPORT (A-20-S)
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-S) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" SHOULDER (24" C.C.) *
TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER
BL
x"
GABLE TRIM (SPT-x)
ROOF PANEL SUPPORT (A-20-L)
(2) 1/4-14 X 7/8"
#12-14 X ____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
INSIDE CLOSURE
**OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET)
1/4-14 X ____" W/O (2 EACH PURLIN)
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
RAKE ANGLE (A-20)
PURLIN
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
STC-MSC Deck Rigid Roof-Wall Gable Field TT
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Field cut outside closure for higher roof pitches. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
RAKE SUPPORT (A-20-S)
1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-S) TRI-BEAD TAPE SEALER STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)
TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER
BL
x"
GABLE TRIM (SPT-x) ROOF PANEL SUPPORT ANGLE (A-20-L)
(2) 1/4-14 X 7/8"
PURLIN
INSIDE CLOSURE
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
#12-14 X _____" (6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE
DECKING
1/4-14 X ____" W/O (2 EACH PURLIN)
PURLIN
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) **** ___ X ___ (2 EACH PURLIN)
*** _____" RIGID BOARD INSULATION (NOT BY CHIEF)
RAKE ANGLE (A-20)
STC-MSC Gable Extension
STC-MSC Gable Extension
STC-MSC Rigid Roof-Wall Gable Ext Lead
NOTES: * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP.) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
PURLIN
BL
GABLE EXTENSION DIMENSION
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN)
TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)
(2) #12-14 X 1 1/4"' PER CLOSURE
* 1/4-14 X 1 1/4" SHOULDER (24" C.C.)
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) (2) 1/4-14 X 7/8" SPECIAL ANGLE (PL-x) RAKE SUPPORT (A-20-S) GABLE TRIM (GTMC)
PURLIN
TOP VIEW
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)
PRE-GLUED THERMAL SPACER
PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) (Optional. Mirror Rake Angle #12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) orientation to avoid insulation break depending on girt/frame orientation.) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE PURLIN CLOSURE (GPC) INSULATION (NOT BY CHIEF) ** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
INSUL.
DEPTH
SPECIAL PLATE (PL-x) (TYP.)
EAVE STRUT
1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)
(2)1/4-14 X 1" (2'-0" C.C.) (TYP.)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) AP SOFFIT PANEL
GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (SPT-x)
PURLIN CLOSURE INSTALLATION
PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8"(12" C.C.)
#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR)
JAMB TRIM (JT)
#12-14 X 1 1/4" (PANCAKE HEAD EACH PURLIN) PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)
1/4-14 X 7/8 (12" C.C.) PANEL CAP TRIM (SCT) INSIDE CLOSURE
WALL PANEL
** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
STC-MSC Height Change
STC-MSC Height Change
STC-MSC Rigid Roof-Wall Gable Height Change Lead
NOTES: * Field cut bottom of wall panels to match roof slope. provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** It is important that fasteners are installed through the center of the slotted holes of the rake support. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER
BL
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) HEIGHT CHANGE TRIM BOTTOM (GHMBF) 1/4-14 X 1 1/4" WT (12" C.C.)
HEIGHT CHANGE ANGLE (PL-x) #12-14 X ____" * WALL PANEL
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER RAKE SUPPORT (A-20-S)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Height Change Isometric Details
* 1 4 "
(NOT BY CHIEF)
***___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) 1/4-14 X _____" W/O (EACH PURLIN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE SUPPORT (A-20-B) *1/4-14 X 1 1/4" SHOULDER (24" C.C.)
2"
INSULATION TO PANEL
PURLIN
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)
STC-MSC Deck Rigid Roof-Wall Gable Height Change Lead
NOTES: * Field cut bottom of wall panels to match roof slope. provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** It is important that fasteners are installed through the center of the slotted holes of the rake support. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. **** See Roof Deck Fastener Details for additional fastener spacing information.
INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER
BL
*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) HEIGHT CHANGE TRIM BOTTOM (GHMBF) 1/4-14 X 1 1/4" WT (12" C.C.)
HEIGHT CHANGE ANGLE (PL-x) #12-14 X ____" * WALL PANEL
(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
STC/MSC ROOF PANEL RAKE SUPPORT (A-20-S)
* 1 4 "
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Height Change Isometric Details
2"
DECKING
INSULATION TO PANEL
RAKE SUPPORT (A-20-B) *1/4-14 X 1 1/4" SHOULDER (24" C.C.)
***___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
1/4-14 X _____" W/O (EACH PURLIN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) **** ___ X ___ (2 EACH PURLIN)
PURLIN
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)
STC-MSC Rigid Roof-Wall High Side Height Change
NOTES: * For screw spacing refer to High Side Height Change detail in the MSC/STC Roof Panel Erection Manual.
INSIDE CLOSURE WALL PANEL
** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.
BL
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
***Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. **** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.
STC/MSC ROOF PANEL BEARING PLATE (HW7500) PRE-GLUED THERMAL SPACER **TRI-BEAD TAPE MASTIC OUTSIDE CLOSURE 1/4-14 X 1 1/4" WT (9 PER PANEL) TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT HEIGHT CHANGE TRIM (LHET) PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Height Change Isometric Details
*** 1 4 "
HEIGHT CHANGE GIRT
x" 3 3/4"
(NOT BY CHIEF)
**** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) #12-14 X 1" PANCAKE HEAD (48" C.C.)
**** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
SPECIAL TRIM (SPT-x) (PW)
BACK-UP PLATE
#12-14 X 1" PANCAKE HEAD (48" C.C.)
4"
8"
INSULATION TO PANEL
PURLIN
STC-MSC Deck Rigid Roof-Wall High Side Height Change
NOTES: * For screw spacing refer to High Side Height Change detail in the MSC/STC Roof Panel Erection Manual.
INSIDE CLOSURE WALL PANEL
BL
** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.
#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
***Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. **** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system. *****See Roof Deck Fastener Details for additional fastener spacing information.
STC/MSC ROOF PANEL BEARING PLATE (HW7500) PRE-GLUED THERMAL SPACER **TRI-BEAD TAPE MASTIC OUTSIDE CLOSURE 1/4-14 X 1 1/4" WT (9 PER PANEL) TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT HEIGHT CHANGE TRIM (LHET) PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
*** 1 4 "
HEIGHT CHANGE GIRT
3 3/4"
DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Height Change Isometric Details
(NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (48" C.C.)
**** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
x"
DECKING
SPECIAL TRIM (SPT-x) (PW)
**** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (48" C.C.)
BACK-UP PLATE
4"
8"
***** ___ X ___ (___" C.C.)
INSULATION TO PANEL
PURLIN