Composite Material, Rigid Board, R-Seal

CS Rigid Roof-Wall High Side Height Change

NOTES: * Provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.

BL

#12-14 X _____" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) INSIDE CLOSURE WALL PANEL

** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)

#12-14 X 1" PANCAKE HEAD (48" C.C.)

1/4-14 X 7/8" WT (12" C.C.) HEIGHT CHANGE TRIM (LHTC)

HEIGHT CHANGE GIRT

2 ROWS DOUBLE BEAD MASTIC TOP & BOTTOM OF OUTSIDE CLOSURE

DRAFTING NOTE: Include Corresponding Standard Details. - Height Change Isometric

CS ROOF PANEL #12-14 X _____" (6" C.C.) OUTSIDE CLOSURE (2" X 3')

* 1 4 "

3 3/4"

x"

1 1

2 "

** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)

INSULATION TO PANEL

SPECIAL TRIM (SPT-x) (PW)

9"

#12-14 X 1" PANCAKE HEAD (48" C.C.)

PURLIN

Made with FlippingBook Annual report maker