Eave and Gable Extensions

MVF-MVP Gable Ext Lead End w AP Soffit

* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN. PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

PURLIN

1

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE TRIM (GTV)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

(2) #12-14 X 1 1/4" (WALL COLOR) PANEL CLIP (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR

DOUBLE BEAD TAPE MASTIC * 1/4-14 X 7/8" WT (12" C.C.)

PANEL CLIP w/FASTENERS

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) MVF/MVP ROOF PANEL

PURLIN

PURLIN

PURLIN CLOSURE (GPC)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2)1/4-14 X 7/8" GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED)

(2) #12-14 X 1 1/4"' PER CLOSURE

#12-14 X 1" PANCAKE HEAD EACH PURLIN

TOP VIEW

GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC)

AP SOFFIT PANEL

PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.) 1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EXTENSION FLASHING (EF) #12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

JAMB TRIM (JT)

EAVE STRUT

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

INSIDE CLOSURE **

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

RAKE ANGLE (A-20-B)

WALL PANEL

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PURLIN CLOSURE INSTALLATION