Eave and Gable Extensions
MVF-MVP Gable Ext Lead End w FSP Soffit
IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER. PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)
** FIELD CUT AROUND PURLINS FOR ATTACHMENT.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN
1
PURLIN CLOSURE (TYP.)
GABLE EXTENSION DIMENSION
BL
GABLE TRIM (GTV)
DOUBLE BEAD TAPE MASTIC * 1/4-14 X 7/8" WT (12" C.C.)
(2) #12-14 X 1 1/4" EACH CLIP (WALL COLOR) (2) #12-14 X 1 1/4'' (WALL COLOR)
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) MVF/MVP ROOF PANEL ** RAKE ANGLE (A-20)
PURLIN
PURLIN PANEL CLIP w/FASTENERS (TYP.)
GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8"
***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN CLOSURE (GPC)
***
(2) #12-14 X 1 1/4"' PER CLOSURE
(2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN #12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
TOP VIEW
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
GABLE EXPANSION TRIM (GET)
1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC)
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS)
EAVE STRUT
FSP SOFFIT PANEL
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
**** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
1/8" X 3/8" BLIND RIVET (12" C.C.)
INSIDE CLOSURE ****
PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)
1/4-14 X 7/8" (12" C.C.)
PURLIN CLOSURE INSTALLATION
WALL PANEL