Eave and Gable Extensions

MVF-MVP Gable Ext Tail End w CS Soffit

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN.

1

ROOF PANEL CUT BACK DIMENSION

GABLE EXTENSION DIMENSION

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

BL

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" PANEL CLIP w/FASTENERS GABLE TRIM (GTV) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP CLIP LOCATION FROM SL

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) * 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC

PURLIN

1 3 4 "

PANEL CLIP w/FASTENERS

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

PURLIN

1"

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN CLOSURE (GPC)

***

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2)1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

MVF/MVP ROOF PANEL

TOP VIEW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.)

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EAVE STRUT

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

#12-14 X 1" PANCAKE HEAD EACH PURLIN EXTENSION FLASHING (EFC)

INSIDE CLOSURE **

JAMB TRIM (JT)

PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.)

PURLIN CLOSURE INSTALLATION

WALL PANEL