Eave and Gable Extensions
MVF-MVP Gable Ext Lead End w AP Soffit and Thermal Spacer
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
* NOTE: This fastener must not hit the purlin.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
GABLE EXTENSION DIMENSION
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
BL
GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" (2) #12-14 X 1 1/4" (WALL COLOR) PANEL CLIP GABLE TRIM (GTVC)
* 1/4-14 X 7/8" WT (6" C.C.) (2) #12-14 X 1 1/4" (EACH CLIP) WALL COLOR
PURLIN
PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN) MVF/MVP ROOF PANEL
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) DOUBLE BEAD TAPE MASTIC PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
PURLIN
THERMAL SPACER (NOT BY CHIEF)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN CLOSURE (GPC)
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED)
(2) #12-14 X 1 1/4"' PER CLOSURE
(NOT BY CHIEF)
TOP VIEW
GABLE EXTENSION CHANNEL (GEC)
EXTENSION FLASHING (EF) #12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
AP SOFFIT PANEL
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)
EAVE STRUT
PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)
INSIDE CLOSURE **
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
#12-14 X 1" PANCAKE HEAD EACH PURLIN
JAMB TRIM (JT) WALL PANEL
PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20-B)
** DRAFTING NOTE: Inside closure must be provided on buildings with Liner Insulation System.
PURLIN CLOSURE INSTALLATION
Made with FlippingBook flipbook maker