Eave and Gable Extensions
Eave Ext Horiz Soff Low MVF-MVP - FSP Soffit w Oversize Gutter and Thermal Spacer
1
* FIELD DRILL 1/4" DIA. HOLE IN GUTTER STRAP, FIELD DRILL 1/8" DIA. PILOT HOLE IN FLAT STRAP IF REQUIRED.
BL
1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT (AT STRAP LOCATIONS) DOUBLE BEAD TAPE MASTIC GUTTER STRAP (GSM) (2'-8" C.C AT PANEL HI-RIBS) * 1/4-14 X 1" (EACH STRAP) TAPE MASTIC
1/4-14 X 1 1/4" WT (4 PER PANEL)
1/4-14 X 1 1/4" WT (4 PER PANEL) MVF-MVP ROOF PANEL PANEL CLIP WITH FASTENERS
"PIG TAIL" TAPE MASTIC (BETWEEN PANELS) (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL
3 3
8 "
** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
EAVE STRUT
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
FLAT STRAP (PL- )
SPECIAL EAVE GUTTER (SPT-) #12-14 X 1 1/4" (TRIM COLOR) 1/8" x 3/8" BLIND RIVET (7-0" C.C.)
**
INSIDE CLOSURE
PRE-GLUED THERMAL SPACER
(NOT BY CHIEF)
INTERMEDIATE PURLIN
#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)
OUTSIDE CLOSURE
SOFFIT PURLIN
1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (SBLTA) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)
TRIM CAP (TCM)
FSP SOFFIT PANEL
SPECIAL TRIM (SPT- )
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/8" X 3/8" BLIND RIVET (12" C.C.) (TYP.) EAVE EXTENSION PURLIN
NOTE: 26 GA FSP SOFFIT MUST HAVE 1/4-14 X 7/8" FASTENERS AT HI-RIB, LOCATED AT SUPPORTS AND MID-SPAN BETWEEN SUPPORTS. SHOW AND CALL OUT FASTENER IF REQUIRED.
WALL PANEL
SPECIAL ANGLE (PL )
NOTE: SOFFIT PURLIN SHOWN REMOVE IF NOT USED. TURN SPECIAL ANGLE FASTENER & TEXT TO BE VISIBLE.