Eave and Gable Extensions

LS Eave Ext Only - Horiz FSP Soffit - MVF-MVP w Oversize Eave Gutter and Thermal Spacer

1

* FIELD DRILL 1/4" DIA. HOLE IN GUTTER STRAP, FIELD DRILL 1/8" DIA. PILOT HOLE IN FLAT STRAP IF REQUIRED.

BL

1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT (AT STRAP LOCATIONS) DOUBLE BEAD TAPE MASTIC GUTTER STRAP (GSM) (2'-8" C.C AT PANEL HI-RIBS) * 1/4-14 X 1" (EACH STRAP) TAPE MASTIC

1/4-14 X 1 1/4" WT (4 PER PANEL)

1/4-14 X 1 1/4" WT (4 PER PANEL) MVF-MVP ROOF PANEL PANEL CLIP WITH FASTENERS

"PIG TAIL" TAPE MASTIC (BETWEEN PANELS) (2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL

3 3

8 "

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

EAVE STRUT

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

FLAT STRAP (PL- )

SPECIAL EAVE GUTTER (SPT-) #12-14 X 1 1/4" (TRIM COLOR) 1/8" x 3/8" BLIND RIVET (7-0" C.C.)

**

INSIDE CLOSURE

PRE-GLUED THERMAL SPACER

(NOT BY CHIEF)

INTERMEDIATE PURLIN

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

OUTSIDE CLOSURE

SOFFIT PURLIN

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) SOFFIT TRIM (SBLTA) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

TRIM CAP (TCM)

FSP SOFFIT PANEL

SPECIAL TRIM (SPT- )

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/8" X 3/8" BLIND RIVET (12" C.C.) (TYP.) EAVE EXTENSION PURLIN

NOTE: 26 GA FSP SOFFIT MUST HAVE 1/4-14 X 7/8" FASTENERS AT HI-RIB, LOCATED AT SUPPORTS AND MID-SPAN BETWEEN SUPPORTS. SHOW AND CALL OUT FASTENER IF REQUIRED.

WALL PANEL

SPECIAL ANGLE (PL )

NOTE: SOFFIT PURLIN SHOWN REMOVE IF NOT USED. TURN SPECIAL ANGLE FASTENER & TEXT TO BE VISIBLE.