Eave and Gable Extensions

STC-MSC Low Side Eave Ext w Eave Trim and CS-AP Soffit and Thermal Spacer

PRE-GLUED THERMAL SPACER FOR EAVE EXTENSION (NOT BY CHIEF) PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

1/4-14 X 1 1/4" WT (8 PER PANEL)

BL

METAL INSIDE CLOSURE TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS

STC/MSC ROOF PANEL

5 1 2 "

* TRAPEZOID PLUG (TRP) AT EACH HIGH RIB

1/4-14 X 1 1/4" WT (6 PER PANEL)

1/4-14 X 7/8" WT (5 PER PANEL)

INTERMED. PURLIN ***

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

EAVE TRIM (ETM)

INSIDE CLOSURE **

1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR) OUTSIDE CLOSURE SOFFIT TRIM (ESTO) 1/4-14 X 7/8" (12" C.C.) WALL PANEL

SOFFIT PANEL 1/4-14 X 1" (2 PER CLOSURE)

EXTENSION FLASHING (EF)

#12-14 X 1 1/4" (12" C.C.)

1/4-14 X 7/8" (12" C.C.) OUTSIDE CLOSURE

* See isometric Trapezoid Plug Installation detail for installation instructions.

DRAFTING NOTES: ** Inside closure must be provided on buildings with liner insulation system. *** If intermediate purlin is required, chg purlin, t-spacer and all fasteners to "dim" layer.