Eave and Gable Extensions
STC-MSC Gable Ext Tail End w FSP Soffit
IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER. ** FIELD CUT AROUND PURLINS FOR ATTACHMENT.
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
GABLE EXTENSION DIMENSION *** DRAFTING NOTE: I NSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
* NOTE: It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.
PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN) PURLIN STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
BL
TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)
PURLIN
GABLE TRIM (GTMC)
* 1/4-14 X 1 1/4" SHOULDER (24" C.C.)
(NOT BY CHIEF)
#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-S) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) (2) 1/4-14 X 7/8"
#12-14 X 1" PANCAKE HEAD (2 PER PURLIN)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
(2) #12-14 X 1 1/4"' PER CLOSURE
PURLIN CLOSURE (GPC)
** RAKE ANGLE (A-20)
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PRE-GLUED THERMAL SPACER **** (NOT BY CHIEF)
TOP VIEW
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) #12-14 X 1"PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.)
EAVE STRUT
(6" C.C. for CS PANEL) (12"C.C. for AP PANEL)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
1/8" X 3/8" BLIND RIVET (12" C.C.) FSP SOFFIT PANEL
INSIDE CLOSURE ***
1/8" X 3/8" BLIND RIVET (12" C.C.) JAMB TRIM/SOFFIT TRIM (JTS)
RAKE ANGLE (A-20-B) PANEL CAP TRIM (SCT)
****DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION
PURLIN CLOSURE INSTALLATION
WALL PANEL
1/4-14 X 7/8" (12" C.C.)
Made with FlippingBook flipbook maker