Eave and Gable Extensions

STC-MSC Gable Ext Tail End-Termination Trim w NO Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

BL

STC/MSC ROOF PANEL * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) TERMINATION TRIM (GTTM)

PANEL CLIP w/FASTENERS

TRI-BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT (24" C.C.) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

PURLIN

PURLIN

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF) PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

TOP VIEW

PURLIN CLOSURE (GPC) #12-14 X 1" PANCAKE HEAD PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

INSIDE CLOSURE **

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC)

EAVE STRUT

#12-14 X 1 1/4" (12" C.C.) EXTENSION FLASHING (EF) #12-14 X 1 1/4" PANCAKE HEAD EACH PURLIN

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

WALL PANEL

DRAFTING NOTES: ** Inside closure must be provided on buildings with liner insulation system. *** Thermal spacer to be used with no insulation.

PURLIN CLOSURE INSTALLATION

* It is important that 1/4-14 x 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.