Eave and Gable Extensions

STC-MSC Gable Ext Tail End -Term Trim w NO Soffit and Thermal Spacer

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

TRI-BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTM) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION

PANEL CLIP w/FASTENERS

PURLIN

PURLIN

(NOT BY CHIEF)

THERMAL SPACER

STC/MSC ROOF PANEL

(NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE (GPC)

**

INSIDE CLOSURE

TOP VIEW

#12-14 X 1" PANCAKE HEAD (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE

(2) 1/4-14 X 7/8"

#12-14 X 1" PANCAKE HEAD EACH PURLIN GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EAVE STRUT

WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

EXTENSION FLASHING (EF)

* It is important that 1/4-14 x 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

#12-14 X 1 1/4" (12" C.C.)

DRAFTING NOTE: ** Inside closure must be provided on buildings with liner insulation system.

PURLIN CLOSURE INSTALLATION