Eave and Gable Extensions

STC-MSC Gable Ext Tail End w CS Soffit and Thermal Spacer

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

* NOTE: It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

BL

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMC)

PURLIN

PURLIN

STC/MSC ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(NOT BY CHIEF)

THERMAL SPACER

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE (GPC)

(NOT BY CHIEF)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.) JAMB TRIM (JT) 1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

EXTENSION FLASHING (EFC)

INSIDE CLOSURE **

WALL PANEL

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN

PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION