STC MSC Roof Panel

MSC 2-Inch-Inset Gable Lead Height Change-Panel Below-Thermal Spacer

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

HEIGHT CHANGE ANGLE (A-20-H) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) *WALL PANEL

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

PURLIN

1/4-14 X 1 1/4" WT (12" C.C.) MSC ROOF PANEL THERMAL SPACER

1

4 "

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

RAKE SUPPORT (A-20-2)

(NOT BY CHIEF)

PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

HEIGHT CHANGE RAFTER

HEIGHT CHANGE TRIM BOTTOM (GHMBF) 1/4-14 X 1 1/4" SHOULDER (24" C.C.)** PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN) (2) #12-24 X 1 1/2" AT 36" C.C. PANEL CAP TRIM (SCT) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

TOP VIEW

2"

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION