STC MSC Roof Panel
STC-MSC Outset Gable Lead Height Change w Panel Below
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE
** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.
* WALL PANEL (TYP.)
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
BL
CLOSURE CLIPS (GCC-1) (TYP.)
HEIGHT CHANGE ANGLE (A-20-H)
PURLIN CLOSURE (TYP.)
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C,C, for AP PANEL) RAKE SUPPORT (A-20-S)
1/4-14 X 1 1/4" WT (12" C.C.)
PURLIN
PURLIN
PURLIN CLOSURE (PURLIN CLOSURE CLIPS NOT SHOWN)
STC/MSC ROOF PANEL
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
1
4 "
***
PRE-GLUED THERMAL SPACER (NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
TOP VIEW
HEIGHT CHANGE TRIM BOTTOM (GHMBF)
2"
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.
1/4-14 X 1 1/4" SHOULDER (24" C.C.)** #12-14 X 1 1/4" (GA) (2 EACH PURLIN)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
PANELING CAP TRIM (SCT) RAKE ANGLE (A-20) HEIGHT CHANGE RAFTER 1/4-14 X 7/8" (12" C.C.)
EAVE STRUT
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)
PURLIN CLOSURE INSTALLATION