STC MSC Roof Panel
STC-MSC High Side Height Change w Zee Girt and Panel Below
WALL PANEL (TYP.)
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B)
INSIDE CLOSURE
(2) #12-14 X 1 1/4" (GA) (36" C.C.)
BL
HEIGHT CHANGE GIRT
TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT HEIGHT CHANGE TRIM (LHET)
TRI-BEAD TAPE MASTIC OUTSIDE CLOSURE 1/4-14 X 1 1/4" WT (9 PER PANEL)
1
4 "
PRE-TAPED THERMAL SPACER (NOT BY CHIEF) *** PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
STC/MSC ROOF PANEL
DRAFTING NOTE: *** Thermal spacer to be used with no insulation. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll. * For screw spacing refer to High Side Height Change detail in the MSC/STC Roof Panel Erection Manual. Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
PURLIN
BACK-UP PLATE
4"
8"