STC MSC Roof Panel

STC-MSC Outset Gable Lead Height Change w Panel Below and Thermal Spacer

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

HEIGHT CHANGE ANGLE (A-20-H) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) * WALL PANEL

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

BL

PURLIN

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

RAKE SUPPORT (A-20-T)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

1/4-14 X 1 1/4" WT (12" C.C.) STC/MSC ROOF PANEL THERMAL SPACER

(2) #12-14 X 1 1/4"' PER CLOSURE

1

4 "

PURLIN CLOSURE (PURLIN CLOSURE CLIPS NOT SHOWN)

(NOT BY CHIEF)

TOP VIEW

PURLIN

HEIGHT CHANGE TRIM BOTTOM (GHMBF) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

2"

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** #12-14 X 1 1/4" (GA) (2 EACH PURLIN)

EAVE STRUT

RAKE ANGLE (A-20) HEIGHT CHANGE RAFTER 1/4-14 X 7/8" (12" C.C.) PANELING CAP TRIM (SCT)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION