STC MSC Roof Panel
STC-MSC Fixed Mid-Slope-Low Floating Eave and Eave Gutter
METAL INSIDE CLOSURE *(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)
** TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)
BL
?
1/4-14 X 1" (2 PER CLOSURE)
6"
DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM)
FLOATING EAVE PLATE
#12-14 X 1 1/4" (TRIM COLOR) GUTTER STRAP (GSM) AT EACH PANEL HI-RIB
EQ. EQ.
1 1 2 " MIN.
***
STC/MSC ROOF PANEL
1/4-14 X 7/8" WT (6" C.C.)
EAVE STRUT ****
EAVE GUTTER (EGM)
1/4 - 14 X 1 1/4" SHOULDER (12" C.C.) FASTENER MUST BE CENTERED IN SLOT TRI-BEAD TAPE MASTIC
SPECIAL TRIM (SPT- ) 1/4-14 X 7/8" (12" C.C.) INSIDE CLOSURE ***** #12-14 X 1 1/4" (__" C.C.) WALL PANEL
* Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT between gutter strap and roof panel. ** See isometric Trapezoid Plug Installation detail for installation instructions. *** Maintain 1 1/2" minimum from face of cap trim to panel screw
DRAFTING NOTES: **** Eave strut on STC/MSC roof floating eave High Clip = CS standard ES no offset key plan type S. ***** Inside closure must be provided on buildings with liner insulation system.