Eave and Gable Extensions

MVF-MVP Gable Ext Tail End w FSP Soffit and Thermal Spacer

* NOTE: This fastener must not hit the purlin. ** Field cut around purlins for attachment.

If sub-framing at gable extension exceeds 4'-0 spacing then an A-20 angle will be sent and field cut around purlins for attachment. Fasteners for angle to purlin and soffit to angle will be sent. Change angle and fasteners to "DIM" layer.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLIP LOCATION FROM S ROOF PANEL CUT BACK DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (TYP.)

BL

#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) * 1/4-14 X 1 1/4" WT (6" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION

L

GABLE TRIM (GTVC)

PANEL CLIP WITH FASTENERS (TYP.) (SEE ROOF PANEL PLAN)

1 3 4 "

#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" 1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (12" C.C.) FSP SOFFIT PANEL

THERMAL SPACER MVF/MVP ROOF PANEL

PURLIN

1"

(NOT BY CHIEF)

PURLIN CLOSURE (GPC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

PURLIN

(NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

** RAKE ANGLE (A-20)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1" PANCAKE HEAD (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)

EAVE STRUT

INSIDE CLOSURE ***

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/8" X 3/8" BLIND RIVET (12" C.C.) 1/4-14 X 7/8" (12" C.C.) JAMB TRIM/SOFFIT TRIM (JTS)

RAKE ANGLE (A-20-B) PANEL CAP TRIM (SCT)

WALL PANEL

NOTE: 26 GA FSP soffit must always have 1/4-14 x 7/8" fasteners located at ribs at end supports. Change fasteners to "DIM" layer.

*** DRAFTING NOTE: Inside closure must be provided on buildings with Liner Insulation System.

PURLIN CLOSURE INSTALLATION