Eave and Gable Extensions
MVF-MVP Gable Ext Tail End w FSP Soffit and Thermal Spacer
PANEL CLIP WITH FASTENERS (TYP.) IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.
** FIELD CUT AROUND PURLINS FOR ATTACHMENT.
GABLE TRIM (GTV) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4" (WALL COLOR) EACH CLIP CLIP LOCATION FROM S ROOF PANEL CUT BACK DIMENSION #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" * NOTE: THIS FASTENER MUST NOT HIT THE PURLIN. L
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
1
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
CLOSURE CLIPS (GCC-1) (TYP.)
GABLE EXTENSION DIMENSION
PURLIN CLOSURE (TYP.)
BL
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) * 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
1 3 4 "
THERMAL SPACER MVF/MVP ROOF PANEL
PURLIN
1"
(NOT BY CHIEF)
PURLIN CLOSURE (GPC)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
PURLIN
(NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
** RAKE ANGLE (A-20)
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
#12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) 1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (12" C.C.) FSP SOFFIT PANEL
TOP VIEW
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
#12-14 X 1" PANCAKE HEAD (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)
EAVE STRUT
INSIDE CLOSURE ***
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
1/8" X 3/8" BLIND RIVET (12" C.C.) 1/4-14 X 7/8" (12" C.C.) JAMB TRIM/SOFFIT TRIM (JTS)
RAKE ANGLE (A-20-B) PANEL CAP TRIM (SCT)
WALL PANEL
NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.
*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
PURLIN CLOSURE INSTALLATION