Eave and Gable Extensions

STC-MSC Gable Ext Lead End w FSP Soffit

** FIELD CUT AROUND PURLINS FOR ATTACHMENT.

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE CLIP.

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

GABLE EXTENSION DIMENSION

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) STC/MSC ROOF PANEL ** RAKE ANGLE (A-20)

PANEL CLIP w/FASTENERS

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM)

PURLIN

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF) PRE-GLUED THERMAL SPACER **** (NOT BY CHIEF)

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE (GPC) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

TOP VIEW

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

#12-14 x 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION)

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS) #12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

FSP SOFFIT PANEL

EAVE STRUT

INSIDE CLOSURE ***

1/8" X 3/8" BLIND RIVET (12" C.C.)

PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER. ****DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

WALL PANEL

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

PURLIN CLOSURE INSTALLATION