Eave and Gable Extensions

STC-MSC Gable Ext Tail End-Termination Trim w AP Soffit

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

TRI-BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.) TERMINATION TRIM (GTTM) 1/4-14 x 1 1/4" WT (24" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM)

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (TYP.)

BL

STC/MSC ROOF PANEL PANEL CLIP w/FASTENERS

#12-14 x 1 1/4" PANCAKE HEAD EACH PURLIN * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)

PURLIN

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

PURLIN

PURLIN CLOSURE (GPC)

#12-14 x 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 x 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 x 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR)

TOP VIEW

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

AP SOFFIT PANEL

GABLE EXPANSION TRIM (GET)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)

PANEL SUPPORT TRIM (SSP) 1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

INSIDE CLOSURE **

JAMB TRIM (JT) DRAFTING NOTES: ** Inside closure must be provided on buildings with liner insulation system. *** Thermal spacer to be used with no insulation.

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

* It is important that 1/4-14 x 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

PURLIN CLOSURE INSTALLATION

WALL PANEL