Eave and Gable Extensions

STC-MSC Gable Ext Tail End -Field Bend Vertical Leg w CS Soffit and Thermal Spacer

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTM) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

1

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (TYP.)

BL

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

(NOT BY CHIEF)

THERMAL SPACER STC/MSC ROOF PANEL

PURLIN

PURLIN

PANEL CLIP w/FASTENERS

(NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

PURLIN CLOSURE (GPC)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.) JAMB TRIM (JT) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EXTENSION FLASHING (EFC)

EAVE STRUT

(6" C.C. for CS PANEL) (12" C.C.for AP PANEL)

WALL PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

#12-14 X 1 1/4" (12" C.C.) #12-14 X 1" PANCAKE HEAD EACH PURLIN

** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

INSIDE CLOSURE **

RAKE ANGLE (A-20-B)

PURLIN CLOSURE INSTALLATION