Eave and Gable Extensions
STC-MSC Gable Ext Tail End -Term Trim w NO Soffit and Thermal Spacer
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
GABLE EXTENSION DIMENSION
CLOSURE CLIPS (GCC-1) (TYP.)
#12-14 X 1" PANCAKE HEAD EACH PURLIN GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMC) (2) 1/4-14 X 7/8" TRI-BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.) TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.)
PURLIN CLOSURE (TYP.)
BL
TRI-BEAD TAPE MASTIC 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
PANEL CLIP w/FASTENERS (SEE ROOF PANEL PLAN)
PURLIN
PURLIN
THERMAL SPACER
(NOT BY CHIEF)
STC/MSC ROOF PANEL
(NOT BY CHIEF)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
(2) #12-14 X 1 1/4"' PER CLOSURE
PURLIN CLOSURE (GPC)
**
INSIDE CLOSURE
TOP VIEW
#12-14 X 1" PANCAKE HEAD (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) FIELD NOTCH AS REQUIRED AT EACH PURLIN ROW
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
EAVE STRUT
WALL PANEL
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
* It is important that 1/4-14 x 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.
EXTENSION FLASHING (EF)
DRAFTING NOTE: ** Inside closure must be provided on buildings with liner insulation system.
#12-14 X 1 1/4" (12" C.C.)
PURLIN CLOSURE INSTALLATION