STC MSC Roof Panel
MSC 2-Inch-Outset Gable Tail Height Change-Special Trim-Panel Below-Thermal Spacer
PURLIN
* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.
*WALL PANEL
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
INSIDE CLOSURE SPECIAL TRIM (SPT- )
BL
CLOSURE CLIPS (GCC-1) (TYP.)
HEIGHT CHANGE ANGLE (A-20-H)
PURLIN CLOSURE (TYP.)
TRI-BEAD TAPE MASTIC
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)
PURLIN
1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)
PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
1
4 "
THERMAL SPACER MSC ROOF PANEL
#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)
(2) #12-14 X 1 1/4"' PER CLOSURE
(NOT BY CHIEF)
PURLIN
TOP VIEW
HEIGHT CHANGE TRIM BOTTOM (GHMBF)
PURLIN CLOSURE (GPC___) (PURLIN CLOSURE CLIPS NOT SHOWN)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (GA) (2 EACH PURLIN)
EAVE STRUT
PANELING CAP TRIM (SCT)
SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING)
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
RAKE ANGLE (A-20)
HEIGHT CHANGE RAFTER
PURLIN CLOSURE INSTALLATION