STC MSC Roof Panel

Common details and conditions for STC and MSC roof system applications.

STC/MSC Roof Panel Sections & Details

All details downloadable in .dwg and .pdf

Table of Contents

STC-MSC Roof - Eave STC-MSC Eave Isometric w Gutter STC-MSC Eave Low Side Gutter

STC-MSC Eave Low Side Gutter No Wall Panel STC-MSC Eave Low Side Gutter Oversized STC-MSC Eave Isometric w Eave Trim STC-MSC Eave Low Side Eave Trim STC-MSC Eave High Side Eave Trim Thermal Spacer

STC-MSC Eave Isometric w Trim Cap STC-MSC Eave Low Side Trim Cap Only STC-MSC Roof - Gable - Short Clip

STC-MSC Gable Lead End STC-MSC Gable Tail End STC-MSC Gable Lead End Vertical Leg Set Back from Building Line and Termination Trim

STC-MSC Gable Tail End Termination Trim STC-MSC Gable End Field Bend Vertical Leg

STC-MSC Gable End Field Bend Vertical Leg and Termination Trim STC-MSC Roof - Gable - Tall Clip (w Thermal Spacer)

STC-MSC Gable Lead End Thermal Spacer STC-MSC Gable Tail End and Thermal Spacer STC-MSC Gable Lead End Vertical Leg Set Back from Building Line-Term Trim and Thermal Spacer STC-MSC Gable Tail End Termination Trim and Thermal Spacer STC-MSC Gable End Field Bend Vertical Leg and Thermal Spacer STC-MSC Gable End Field Bend Vertical Leg-Termination Trim and Thermal Spacer STC-MSC Roof - Height Change - Short Clip STC-MSC Inset Gable Lead Height Change

STC-MSC Inset Gable Lead Height Change w Panel Below STC-MSC Inset Gable Height Change w Field Bend Vertical Leg STC-MSC Inset Gable Height Change w Field Bend Vertical Leg with Panel Below STC-MSC Inset Gable Height Change w Set Back Field Bend Vertical Leg STC-MSC Inset Gable Tail Height Change STC-MSC Inset Gable Tail Height Change w Panel Below STC-MSC Inset Gable Tail Height Change w Special Trim STC-MSC Inset Gable Tail Height Change w Special Trim and Panel Below STC-MSC Outset Gable Height Change w Field Bend Vertical Leg with Panel Below STC-MSC Outset Gable Tail Height Change w Special Trim and Panel Below STC-MSC High Side Height Change w Cee Girt STC-MSC High Side Height Change w Cee Girt and Panel Below STC-MSC Outset Gable Lead Height Change w Panel Below STC-MSC Outset Gable Tail Height Change w Panel Below

Table of Contents

STC-MSC High Side Height Change w Zee Girt STC-MSC High Side Height Change w Zee Girt and Panel Below STC-MSC Roof - Height Change - Tall Clip (w Thermal Spacer) STC-MSC Inset Gable Lead Height Change and Thermal Spacer STC-MSC Inset Gable Lead Height Change w Panel Below and Thermal Spacer STC-MSC Inset Gable Height Change w Field Bend Vertical Leg and Thermal Spacer STC-MSC Inset Gable Height Change w Field Bend Vertical Leg with Panel Below and Thermal Spacer STC-MSC Inset Gable Height Change w Set Back Field Bend Vertical Leg and Thermal Spacer STC-MSC Inset Gable Tail Height Change and Thermal Spacer STC-MSC Inset Gable Tail Height Change w Panel Below and Thermal Spacer STC-MSC Inset Gable Tail Height Change w Special Trim and Thermal Spacer STC-MSC Inset Gable Tail Height Change w Special Trim- Panel Below and Thermal Spacer STC-MSC Outset Gable Height Change w Field Bend Vertical Leg w Panel Below and Thermal Spacer STC-MSC Outset Gable Tail Height Change w Special Trim- Panel Below and Thermal Spacer STC-MSC High Side Height Change w Cee Girt and Thermal Spacer STC-MSC High Side Height Change w Cee Girt-Panel Below and Thermal Spacer STC-MSC High Side Height Change w Zee Girt and Thermal Spacer STC-MSC High Side Height Change w Zee Girt-Panel Below and Thermal Spacer STC-MSC Roof - Existing Building - Short Clip STC-MSC Gable End Field Bend Vertical Leg - Taller Existing Building STC-MSC Gable Lead End to Taller Existing Building STC-MSC Gable Tail End Special Trim - Taller Existing Building STC-MSC Gable Tail End to Taller Existing Building STC-MSC High Side - Taller Existing Building STC-MSC Roof - Existing Building - Tall Clip (w Thermal Spacer) STC-MSC Gable End Field Bend Vertical Leg - Taller Existing Building and Thermal Spacer STC-MSC Gable Lead End to Taller Existing Building and Thermal Spacer STC-MSC Gable Tail End Special Trim - Taller Existing Building and Thermal Spacer MSC Fixed Mid-Slope Purlin STC Fixed Mid-Slope Joist STC-MSC Fixed Mid-Slope-Low Floating Eave and Eave Gutter STC-MSC Fixed Mid-Slope-Low Floating Eave and Oversize Eave Gutter STC-MSC Fixed Mid-Slope-High Floating Eave w Thermal Spacer and Eave Gutter STC-MSC Fixed Mid-Slope-High Floating Eave w Thermal Spacer and Oversize Eave Gutter STC-MSC Roof - Roof Panel Splice STC-MSC Outset Gable Lead Height Change w Panel Below and Thermal Spacer STC-MSC Outset Gable Tail Height Change w Panel Below and Thermal Spacer STC-MSC Gable Tail End to Taller Existing Building and Thermal Spacer STC-MSC High Side - Taller Existing Building with Thermal Spacer STC-MSC Roof - Fixed Mid-Slope

Table of Contents

SCREW_208.STC Panel Splice SCREW_209.MSC Panel Splice STC-MSC Roof - Nichiha Wall Panel STC-MSC Eave Gutter and Nichiha Panel Not by Chief STC-MSC Gable End w Field Bend Vertical Leg and Nichiha Panel Not by Chief

STC-MSC Gable End w Field Bend Vertical Leg and Termination Trim and Nichiha Panel NBC STC-MSC Gable End w Vert Leg Set Back from Bldg Line and Term Trim and Nichiha Panel NBC

STC-MSC Gable Lead End and Nichiha Panel Not by Chief STC-MSC Gable Tail End and Nichiha Panel Not by Chief STC-MSC Gable Tail End w Termination Trim and Nichiha Panel Not by Chief

STC-MSC Gable End w Field Bend Vert Leg and Term Trim Thermal Spacer and Nichiha Panel NBC STC-MSC Gable End w Field Bend Vertical Leg Thermal Spacer and Nichiha Panel Not by Chief STC-MSC Gable End w Vert Leg from Bldg Line and Term Trim Thermal Spacer and Nichiha Panel NBC STC-MSC Gable Lead End w Thermal Spacer and Nichiha Panel Not by Chief STC-MSC Gable Tail End w Termination Trim Thermal Spacer and Nichiha Panel Not by Chief STC-MSC Gable Tail End w Thermal Spacer and Nichiha Panel Not by Chief MSC Roof - 2-inch Standoff Clip - Eave MSC 2-Inch-Low Side-Eave Gutter MSC 2-Inch-Low Side-Eave Gutter-No Wall Panel MSC 2-Inch-Low Side-Oversize Eave Gutter MSC 2-Inch-Low Side-Trim Cap Only MSC 2-Inch-Isometric Installation of Trapezoid Plug-Eave Gutter MSC 2-Inch-Isometric Installation of Trapezoid Plug-Low Side-Eave Trim MSC 2-Inch-High Side-Eave Trim MSC Roof - 2-inch Standoff Clip - Gable MSC 2-Inch-Gable Lead End-Thermal Spacer MSC 2-Inch-Gable Lead End-Vertical Leg Set Back from Building Line-Term Trim-Thermal Spacer MSC 2-Inch-Gable Tail End-Thermal Spacer MSC 2-Inch-Gable Tail End with Termination Trim-Thermal Spacer MSC 2-Inch-Gable End-Field Bend Vertical Leg-Thermal Spacer MSC 2-Inch-Gable End-Field Bend Vertical Leg-Termination Trim-Thermal Spacer MSC Roof - 2-inch Standoff Clip - Height Change MSC 2-Inch-Inset Gable Lead Height Change-Thermal Spacer MSC 2-Inch-Inset Gable Lead Height Change-Panel Below-Thermal Spacer MSC 2-Inch-Inset Gable Tail Height Change-Thermal Spacer MSC 2-Inch-Inset Gable Tail Height Change-Panel Below-Thermal Spacer MSC 2-Inch-Inset Gable Tail Height Change-Special Trim-Thermal Spacer MSC 2-Inch-Inset Gable Tail Height Change-Special Trim-Panel Below-Thermal Spacer MSC 2-Inch-High Side-Eave Trim-Thermal Spacer MSC 2-Inch-Gable Extension-High Side-NO Soffit

Table of Contents

MSC 2-Inch-Inset Gable Height Change-Field Bend Vertical Leg-Thermal Spacer MSC 2-Inch-Inset Gable Height Change-Field Bend Vertical Leg-Panel Below-Thermal Spacer MSC 2-Inch-Inset Gable Height Change-Special Set Back-Field Bend Vertical Leg-Thermal Spacer

MSC 2-Inch-Outset Gable Lead Height Change-Panel Below-Thermal Spacer MSC 2-Inch-Outset Gable Tail Height Change-Panel Below-Thermal Spacer

MSC 2-Inch-Outset Gable Tail Height Change-Special Trim-Panel Below-Thermal Spacer MSC 2-Inch-Outset Gable Height Change-Field Bend Vertical Leg-Panel Below-Thermal Spacer MSC 2-Inch-High Side Height Change-Cee Girt-Thermal Spacer MSC 2-Inch-High Side Height Change-Cee Girt-Panel Below-Thermal Spacer MSC 2-Inch-High Side Height Change-Zee Girt-Thermal Spacer MSC 2-Inch-High Side Height Change-Zee Girt-Panel Below-Thermal Spacer MSC Roof - 2-inch Standoff Clip - Existing Building MSC 2-Inch-Gable Lead End-Taller Existing Building MSC 2-Inch-Gable Lead End-Taller Existing Building-Thermal Spacer MSC 2-Inch-Gable Tail End-Taller Existing Building MSC 2-Inch-Gable Tail End-Taller Existing Building-Thermal Spacer MSC 2-Inch-Gable End-Field Bend Vertical Leg-Taller Existing Building MSC 2-Inch-Gable End-Field Bend Vertical Leg-Taller Existing Building-Thermal Spacer MSC 2-Inch-Gable Tail End-Special Trim-Taller Existing Building MSC 2-Inch-Gable End-Field Bend Vertical Leg-Taller Existing Building-Thermal Spacer MSC 2-Inch-High Side-Taller Existing Building MSC 2-Inch-High Side-Taller Existing Building-Thermal Spacer

STC-MSC Roof - Eave

STC-MSC Roof Eave

STC-MSC Eave Isometric w Gutter

(20) 1/8" X 3/8" BLIND RIVETS

STC/MSC ROOF PANEL

STC/MSC ROOF PANEL

GABLE TRIM (GTM)

GABLE TRIM (GTM)

GUTTER STRAP (GSM) (FASTENERS NOT SHOWN)

*DOUBLE BEAD TAPE MASTIC

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

(12) 1/8" X 3/8" BLIND RIVETS

EAVE GUTTER (EGM)

*TRAPEZOID PLUG (TRP)

GABLE TRIM PLUG (TPRM/TPLM)

2" STRIP OF MINOR RIB TAPE SEALER (TYP.)

GABLE CORNER TRIM (GCTM)

GABLE EXPANSION TRIM (GET)

NOTE: 1. USE 1 1/2" LAP AT SPLICES, AND FIELD CUT 3/8" LOCKFORM AT SPLICE. 2. FASTEN SPLICE WITH (12) 1/8" X 3/8" BLIND RIVETS. 3. USE SIKA 511 SEALANT AT SPLICE.

NOTE: 1. START GABLE TRIM 3" OUT FROM END OF ROOF PANEL. 2. START EAVE GUTTER 3" OUT FROM ENDWALL BUILDING LINE. 3. LOCATE GABLE TRIM PLUG AGAINST HIGH-RIB OF CS ENDWALL PANEL OR FLAT OF AP ENDWALL PANEL. 4. USE SIKA 511 SEALANT AT PLUG AND CORNER TRIM TO GUTTER.

EAVE GUTTER (EGM)

*EDGE OF MASTIC ALIGNS WITH FACE OF TRAPEZOID PLUG

DOUBLE BEAD TAPE MASTIC

GABLE TRIM SPLICE

TRAPEZOID PLUG INSTALLATION WITH GUTTER

GABLE CORNER TRIM WITH GUTTER

STC-MSC Eave Low Side Gutter

STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE *(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) **TRAPEZOID PLUG (TRP) EACH HIGH RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) GUTTER STRAP (GSM) AT EACH PANEL HI-RIB

BL

4 1 2 "

#12-14 X 1 1/4" (TRIM COLOR)

EAVE STRUT

1/4-14 X 7/8" (12" C.C) TRIM CAP (TCM) EAVE GUTTER (EGM) 1/4-14 X 7/8" WT (6" C.C.)

* Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" WT's between gutter strap and roof panel. ** See Isometric Trapezoid Plug Installation detail for installation instructions. DRAFTING NOTE: *** Inside closure must be provided on buildings with liner insulation. system.

INSIDE CLOSURE

***

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

WALL PANEL

STC-MSC Eave Low Side Gutter No Wall Panel

1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE **(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)

TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)

BL

*TRAPEZOID PLUG (TRP) EACH HIGH RIB

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM)

4 1 2 "

GUTTER STRAP (GSM) AT EACH PANEL HI-RIB

STC/MSC ROOF PANEL

#12-14 X 1 1/4" (TRIM COLOR)

EAVE STRUT

EAVE GUTTER (EGM) 1/4-14 X 7/8" WT (6" C.C.)

DRAFTING NOTES: *** TRIM CAP TO COVER WEB DEPTH. * See isometric Trapezoid Plug Installation detail for installation instructions. ** Field cut (1) 2" long strip of tri-bead tape mastic & center in panel seam above metal inside closure.

***

SPECIAL TRIM (SPT- ) #12-14 X 1 1/4" (12" C.C.)

STC-MSC Eave Low Side Gutter Oversized

1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL) 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS *(2) 1/4-14 X 7/8" WT GUTTER STRAP TO ROOF PANEL METAL INSIDE CLOSURE 1/4-14 X 1" (2) PER CLOSURE STC/MSC ROOF PANEL

***TRAPEZOID PLUG (TRP) EACH HI-RIB TRI-BEAD TAPE MASTIC (TOP AND BOTTOM) 1/4-14 X 7/8" WT (6" C.C) (1/4-14 X 1" AT FLAT STRAP)

BL

7 15 16 "

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM) GUTTER STRAP (GSM) AT EACH HI-RIB FLAT STRAP (PL- )

4 1 2 "

EAVE STRUT

#12-14 X 1 1/4" (TRIM COLOR) (EACH STRAP) ** 1/4-14 X 1"

(EACH STRAP) SPECIAL EAVE

* Field cut (2) 2" long strips of tri-bead tape mastic & center under 1/4-14 x 7/8" wt's between gutter strap and roof panel. ** Field drill 1/4" dia. hole in gutter strap, field drill 1/8" dia. pilot hole in flat strap if required. *** See Isometric Trapezoid Plug Installation detail for installation instructions. DRAFTING NOTE: **** Inside closure must be provided on buildings with liner insulation system.

GUTTER (SPT- ) TRIM CAP (TCM) 1/4-14 X 7/8" (12" C.C.)

****

INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) WALL PANEL

STC-MSC Eave Isometric w Eave Trim

STC/MSC ROOF PANEL

(19) 1/8" X 3/8" BLIND RIVETS

STC/MSC ROOF PANEL

GABLE TRIM (GTM)

GABLE TRIM (GTM)

*DOUBLE BEAD TAPE MASTIC

EAVE TRIM (ETM)

*TRAPEZOID PLUG (TRP)

(12) 1/8" X 3/8" BLIND RIVETS

GABLE TRIM PLUG (TPRM/TPLM)

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

GABLE CORNER TRIM (GCTM)

2" STRIP OF MINOR RIB TAPE SEALER (TYP.)

NOTE: 1. START GABLE TRIM BOTTOM LEG 4" OUT FROM SIDEWALL BUILDING LINE. 2. START EAVE TRIM 3" OUT FROM ENDWALL BUILDING LINE. 3.) LOCATE GABLE TRIM PLUG AGAINST HIGH-RIB OF CS ENDWALL PANEL OR FLAT OF AP ENDWALL PANEL. 4. FIELD CUT ROOF PANEL AT GABLE CORNER TRIM. (AS REQUIRED) 5. USE SIKA 511 SEALANT AT PLUG AND GABLE CORNER TRIM TO EAVE TRIM. GABLE CORNER TRIM WITH EAVE TRIM

GABLE EXPANSION TRIM (GET)

NOTE: 1. USE 1 1/2" LAP AT SPLICES, AND FIELD CUT 3/8" LOCKFORM AT SPLICE. 2. FASTEN SPLICE WITH (12) 1/8" X 3/8" BLIND RIVETS. 3. USE SIKA 511 SEALANT AT SPLICE.

EAVE TRIM (ETM)

*EDGE OF MASTIC ALIGNS WITH FACE OF TRAPEZOID PLUG

DOUBLE BEAD TAPE MASTIC

GABLE TRIM SPLICE

TRAPEZOID PLUG INSTALLATION WITH EAVE TRIM

STC-MSC Eave Low Side Eave Trim

PANEL OVERHANG PITCH 0:12 to 2 3/8:12 >2 3/8:12 to 4:12 ALL DIMENSIONS IN INCHES 5 1/2 6 1/2

1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)

TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)

BL

1/4-14 X 7/8" WT (5 PER PANEL)

* TRAPEZOID PLUG (TRP) EACH HIGH RIB

STC/MSC ROOF PANEL

DOUBLE BEAD TAPE MASTIC (TOP AND BOTTOM)

EAVE TRIM (ETM)

EAVE STRUT

1/4-14 X 7/8" (12" C.C.) TRIM CAP (TCM)

DRAFTING NOTE: ** Inside closure must be provided on buildings with liner insulation system. * See isometric Trapezoid Plug Installation detail for installation instructions.

INSIDE CLOSURE

**

OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

WALL PANEL

STC-MSC Eave High Side Eave Trim Thermal Spacer

1/4-14 X 1 1/4" WT (9 PER PANEL) OUTSIDE CLOSURE

TRI-BEAD TAPE MASTIC *1/4-14 X 7/8" WT

BL

**TRI-BEAD TAPE MASTIC

PANEL CLIP W/ FASTENERS (SEE ROOF PANEL PLAN)

2 3 4 "

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) BACK-UP PLATE OUTSIDE CLOSURE INSIDE CLOSURE

THERMAL SPACER

(NOT BY CHIEF)

STC-MSC ROOF PANEL

1/4-14 X 7/8" (12" C.C.) HI-SIDE EAVE TRIM (HETM) 1/4-14 X 7/8" (12" C.C.) EAVE STRUT JAMB TRIM WALL PANEL

* For screw spacing refer to High Eave Trim detail in the MSC/STC Roof Panel Erection Manual. ** 24" STC - Pre-Cut Tri-Bead Tape Mastic. 24" MSC - Tri-Bead Tape Mastic from roll. 18" MSC/STC - Tri-Bead Tape Mastic from roll.

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system.

STC-MSC Eave Isometric w Trim Cap

(15) 1/8" X 3/8" BLIND RIVETS

STC/MSC ROOF PANEL

STC/MSC ROOF PANEL

GABLE TRIM (GTM)

GABLE TRIM (GTM)

TRIM CAP (TCM)

TRIM CAP (TCM)

TRI-BEAD TAPE MASTIC UNDER METAL INSIDE CLOSURE

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

GABLE TRIM PLUG (TPRM/TPLM)

(12) 1/8" X 3/8" BLIND RIVETS

*METAL INSIDE CLOSURE (FASTENERS NOT SHOWN)

GABLE CORNER TRIM (GCTM)

GABLE EXPANSION TRIM (GET)

2" STRIP OF MINOR RIB TAPE MASTIC (TYP.)

NOTE: 1. Use 1 1/2" lap at splices, and field cut 3/8" lockform at splice. 2. Fasten splice with (12) 1/8" x 3/8" blind rivets. 3. Use SIKA 511 sealant at splice.

NOTE: 1. Start gable trim even with end of roof panel. 2. Locate gable trim plug against high-rib of cs endwall panel or flat of ap endwall panel. 3. Use SIKA 511 sealant at plug and corner trim.

* Edge of mastic aligns with face of metal inside closure.

TRI-BEAD TAPE MASTIC

GABLE TRIM SPLICE

METAL INSIDE CLOSURE WITH TRIM CAP ONLY

GABLE CORNER TRIM WITH TRIM CAP

STC-MSC Eave Low Side Trim Cap Only

STC/MSC ROOF PANEL 1/4-14 X 1" (2) PER CLOSURE METAL INSIDE CLOSURE 2" STRIP OF TRI-BEAD TAPE MASTIC BETWEEN PANELS 1/4-14 X 1 1/4" WT PANEL TO EAVE (8 PER PANEL)

BL

4 1

2 "

TRI-BEAD TAPE MASTIC (TOP AND BOTTOM)

TRIM CAP (TCM)

EAVE STRUT

1/4-14 X 7/8" (12" C.C.)

*

INSIDE CLOSURE

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

DRAFTING NOTE: * Inside closure must be provided on buildings with liner insulation system.

WALL PANEL

STC-MSC Roof - Gable - Short Clip

STC-MSC Roof Gable Short Clip

STC-MSC Gable Lead End

1/4-14 X 1 1/4" WT (12" C.C.) TRI-BEAD TAPE SEALER

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM)

1

*1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER (NOT BY CHIEF) ****

BL

PURLIN

**** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

INSIDE CLOSURE

***

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

**OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) (2) 1/4-14 X 7/8"

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

* It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support. ** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable Tail End

GABLE TRIM (GTM) RAKE SUPPORT (A-20-S) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) STC/MSC ROOF PANEL

1

BL

****

THERMAL SPACER (NOT BY CHIEF)

INSIDE CLOSURE

***

**** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

* It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support. ** NOTE: Field cut outside closure for higher roof pitches. *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

STC-MSC Gable Lead End Vertical Leg Set Back from Building Line and Termination Trim

1/4-14 X 1 1/4" SHOULDER (24" C.C.) * TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * RAKE SUPPORT (A-20-S) STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER (NOT BY CHIEF) ****

1

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM) TRI-BEAD TAPE SEALER 1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT(24" C.C.) TERMINATION TRIM (GTTM)

BL

PURLIN

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/4-14 X 7/8" INSIDE CLOSURE

***

WALL PANEL **OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

* It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

** NOTE: Field cut outside closure for higher roof pitches.

**** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

STC-MSC Gable Tail End Termination Trim

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM) TRI-BEAD TAPE MASTIC 1/4-14 X 7/8" WT (6" C.C.) 1/4-14 X 1 1/4" WT (24" C.C.) TERMINATION TRIM (GTTM)

*1/4-14 X 1 1/4" SHOULDER (24" C.C.) 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) TRI-BEAD TAPE MASTIC PANEL CLIP W/FASTENERS (REFER TO ROOF PANEL PLAN) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) **** STC/MSC ROOF PANEL

BL

INSIDE CLOSURE

***

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (12" C.C.) **OUTSIDE CLOSURE WALL PANEL GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

** Field cut outside closure for higher roof pitches. * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system. **** Thermal spacer to be used with no insulation.

STC-MSC Gable End Field Bend Vertical Leg

TRI-BEAD TAPE SEALER

STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.)

GABLE TRIM (GTM)

1

RAKE SUPPORT (A-20-S) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

BL

****

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

INSIDE CLOSURE

***

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) **OUTSIDE CLOSURE WALL PANEL

**** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

** NOTE: Field cut outside closure for higher roof pitches. * It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

STC-MSC Gable End Field Bend Vertical Leg and Termination Trim

RAKE SUPPORT (A-20-S)

1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-S) TRI-BEAD TAPE SEALER STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER GABLE TRIM (GTM)

1

BL

RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PURLIN

****

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

**** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

INSIDE CLOSURE

***

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) **OUTSIDE CLOSURE WALL PANEL

* It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

**NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Roof - Gable - Tall Clip (w Thermal Spacer)

STC-MSC Roof Gable Tall Clip (w Thermal Spacer)

STC-MSC Gable Lead End Thermal Spacer

GABLE TRIM (GTM) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER 24" C.C.)* STC/MSC ROOF PANEL THERMAL SPACER

1

BL

(NOT BY CHIEF)

INSIDE CLOSURE

***

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM. * It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

1/4-14 X 7/8" (12" C.C.)

WALL PANEL **OUTSIDE CLOSURE

** NOTE: Field cut outside closure for higher roof pitchs.

STC-MSC Gable Tail End and Thermal Spacer

GABLE TRIM (GTM)

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER (24" C.C.)* STC/MSC ROOF PANEL THERMAL SPACER

1

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE ANGLE (A-20-B) RAKE SUPPORT (A-20-T)

BL

(NOT BY CHIEF)

(2) 1/4-14 X 7/8" INSIDE CLOSURE

***

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

**OUTSIDE CLOSURE WALL PANEL 1/4-14 X 7/8" (12" C.C.) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN * It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

** NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable Lead End Vertical Leg Set Back from Building Line-Term Trim and Thermal Spacer

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER GABLE TRIM (GTM) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1

1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-T) TRI-BEAD TAPE SEALER

BL

STC/MSC ROOF PANEL

THERMAL SPACER (NOT BY CHIEF)

PURLIN

INSIDE CLOSURE

***

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) **OUTSIDE CLOSURE WALL PANEL GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

* It is important that 1/4-14 X 1 1/4" shoulders are installed through the center of the slotted holes of the rake support.

**NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Gable Tail End Termination Trim and Thermal Spacer

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE MASTIC GABLE TRIM (GTM) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

*1/4-14 X 1 1/4" SHOULDER (24" C.C.) 1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP) TRI-BEAD TAPE MASTIC PANEL CLIP W/FASTENERS (REFER TO ROOF PANEL PLAN) STC/MSC ROOF PANEL

BL

****

THERMAL SPACER (NOT BY CHIEF)

INSIDE CLOSURE ***

(2) 1/4-14 X 7/8"

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) WALL PANEL **OUTSIDE CLOSURE GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN

** Field cut outside closure for higher roof pitches. * It is important that 1/4-14 X 1 1/4" SHOULDER fasteners are installed through the center of the slotted holes of the rake support.

DRAFTING NOTES: *** Inside closure must be provided on buildings with liner insulation system. **** Thermal spacer to be used with no insulation.

STC-MSC Gable End Field Bend Vertical Leg and Thermal Spacer

GABLE TRIM (GTM)

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) 1/4-14 X 1 1/4" SHOULDER (24" C.C.)* STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT

1

RAKE SUPPORT (A-20-T)

BL

RAKE ANGLE (A-20-B)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

FINAL DIMENSION) THERMAL SPACER

(NOT BY CHIEF)

INSIDE CLOSURE

***

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM. ** NOTE: Field cut outside closure for higher roof pitches. * It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) (2) 1/4-14 X 7/8" GABLE EXPANSION TRIM (GET)

WALL PANEL **OUTSIDE CLOSURE 1/4-14 X 7/8" (12" C.C.)

STC-MSC Gable End Field Bend Vertical Leg-Termination Trim and Thermal Spacer

TERMINATION TRIM (GTTM) 1/4-14 X 1 1/4" WT (24" C.C.) 1/4-14 X 7/8" WT (6" C.C.) TRI-BEAD TAPE SEALER GABLE TRIM (GTM) RAKE SUPPORT (A-20-T) RAKE ANGLE (A-20-B) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * 1/4-14 X 1 1/4" WT (12" C.C.) RAKE SUPPORT (A-20-T) TRI-BEAD TAPE SEALER STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

1

BL

THERMAL SPACER

(NOT BY CHIEF)

INSIDE CLOSURE

***

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE ANGLE (A-20-B) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) PURLIN *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

(2) 1/4-14 X 7/8"

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

GABLE EXPANSION TRIM (GET) 1/4-14 X 7/8" (12" C.C.) **OUTSIDE CLOSURE WALL PANEL

* It is important that 1/4-14 X 1 1/4" SHOULDERS are installed through the center of the slotted holes of the rake support.

**NOTE: Field cut outside closure for higher roof pitches.

STC-MSC Roof - Height Change - Short Clip

STC-MSC Roof Height Change Short Clip

STC-MSC Inset Gable Lead Height Change

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

* WALL PANEL

BL

HEIGHT CHANGE ANGLE (A-20-H)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) RAKE SUPPORT (A-20-S)

1/4-14 X 1 1/4" WT (12" C.C.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

PURLIN STC ROOF PANEL

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

1

4 "

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** HEIGHT CHANGE TRIM BOTTOM (GHMBF)

2"

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

STC-MSC Inset Gable Lead Height Change w Panel Below

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

* WALL PANEL (TYP.) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

TRI-BEAD TAPE SEALER HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) ***

PURLIN

1

4 "

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

STC/MSC ROOF PANEL

HEIGHT CHANGE ANGLE (A-20-H)

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

(2) #12-14 X 1 1/4"' PER CLOSURE

RAKE SUPPORT (A-20-S)

1/4-14 X 1 1/4" WT (12" C.C.)

2"

TOP VIEW

PURLIN

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

HEIGHT CHANGE RAFTER

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

RAKE ANGLE (A-20)

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

EAVE STRUT

(2) #12-24 X 1 1/2" AT 36" C.C.

1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PANELING CAP TRIM (SCT)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION

STC-MSC Inset Gable Height Change w Field Bend Vertical Leg

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

HEIGHT CHANGE ANGLE (A-20-H) * WALL PANEL

BL

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 1 1/4" WT (12" C.C.)

***

RAKE SUPPORT (A-20-S)

PRE-TAPED THERMAL SPACER (NOT BY CHIEF)

STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

1

4 "

PURLIN

2"

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

**1/4-14 X 1 1/4" SHOULDER (24" C.C.)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

STC-MSC Inset Gable Height Change w Field Bend Vertical Leg with Panel Below

*WALL PANEL

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

PURLIN

RAKE SUPPORT (A-20-S) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

BL

STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

PURLIN

1

4 "

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

HEIGHT CHANGE TRIM BOTTOM (GHMF) 1/4-14 X 1 1/4" WT (12" C.C.)

HEIGHT CHANGE ANGLE (A-20-H)

TOP VIEW

2"

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

PURLIN

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

HEIGHT CHANGE RAFTER

(2) #12-24 X 1 1/2" AT 36" C.C. 1/4-14 X 7/8" (12" C.C.) PANELING CAP TRIM (SCT)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

RAKE ANGLE (A-20)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION

STC-MSC Inset Gable Height Change w Set Back Field Bend Vertical Leg

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

*WALL PANEL

BL

SPECIAL HEIGHT CHANGE TRIM TOP (SPT- )

INSIDE CLOSURE

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER

RAKE SUPPORT (A-20-S) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) SPECIAL HEIGHT CHANGE ANGLE (PL- ) #12-14 x 1 1/4"

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION)

1

4 "

** 1/4-14 X 1 1/4" SHOULDER (24" C.C.)

PURLIN

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

1/4-14 X 1 1/4" WT (12" C.C.) HEIGHT CHANGE TRIM BOTTOM (GHMBF)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

STC-MSC Inset Gable Tail Height Change

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

BL

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) * WALL PANEL

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

RAKE SUPPORT (A-20-S)

1/4-14 X 1 1/4" WT (12" C.C.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

STC/MSC ROOF PANEL PURLIN

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

1

4 "

HEIGHT CHANGE TRIM BOTTOM (GHMBF) 1/4-14 X 1 1/4" SHOULDER (24" C.C.)**

HEIGHT CHANGE ANGLE (A-20-H)

2"

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

STC-MSC Inset Gable Tail Height Change w Panel Below

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

RAKE SUPPORT (A-20-S) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) * WALL PANEL

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

PURLIN

1/4-14 X 1 1/4" WT (12" C.C.)

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

STC/MSC ROOF PANEL

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

(2) #12-14 X 1 1/4"' PER CLOSURE

HEIGHT CHANGE ANGLE (A-20-H)

1

4 "

TOP VIEW

2"

PURLIN

HEIGHT CHANGE RAFTER RAKE ANGLE (A-20)

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

1/4-14 X 1 1/4" SHOULDER (24" C.C.)**

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

EAVE STRUT

PANELING CAP TRIM (SCT) (2) #12-24 X 1 1/2" AT 36" C.C.

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/4-14 X 7/8" (12" C.C.)

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION

STC-MSC Inset Gable Tail Height Change w Special Trim

TRI-BEAD TAPE MASTIC SPECIAL TRIM TOP (SPT- ) INSIDE CLOSURE

BL

*WALL PANEL

HEIGHT CHANGE ANGLE (A-20-H)

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING) (SEE INSET DETAIL)

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION. 1 4 "

STC/MSC ROOF PANEL

**

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

PURLIN

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

PANEL CLIP

DRAFTING NOTE: ** Thermal spacer to be used with no insulation.

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

STC-MSC Inset Gable Tail Height Change w Special Trim and Panel Below

TRI-BEAD TAPE MASTIC SPECIAL TRIM TOP (SPT- ) INSIDE CLOSURE

PURLIN

BL

* FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

*WALL PANEL

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

HEIGHT CHANGE ANGLE (A-20-H)

PURLIN CLOSURE (TYP.)

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING) (SEE INSET DETAIL)

PANEL CLIP #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

DRAFTING NOTE: ** Thermal spacer to be used with no insulation.

1/4-14 X 1 1/4" WT (12" C.C. AND FASTEN THROUGH CLIP)

PURLIN

STC/MSC ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

**

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

1

4 "

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) HEIGHT CHANGE RAFTER RAKE ANGLE (A-20)

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

TOP VIEW

PURLIN

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

PURLIN CLOSURE (GPC__) (PURLIN CLOSURE CLIPS NOT SHOWN)

(2) #12-24 X 1 1/2" AT 36" C.C. PANELING CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION

STC-MSC Outset Gable Lead Height Change w Panel Below

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) TRI-BEAD TAPE SEALER HEIGHT CHANGE TRIM TOP (GHMTF) INSIDE CLOSURE

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

* WALL PANEL (TYP.)

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

BL

CLOSURE CLIPS (GCC-1) (TYP.)

HEIGHT CHANGE ANGLE (A-20-H)

PURLIN CLOSURE (TYP.)

#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C,C, for AP PANEL) RAKE SUPPORT (A-20-S)

1/4-14 X 1 1/4" WT (12" C.C.)

PURLIN

PURLIN

PURLIN CLOSURE (PURLIN CLOSURE CLIPS NOT SHOWN)

STC/MSC ROOF PANEL

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

1

4 "

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) #12-14 X 1 1/4"' PER CLOSURE

TOP VIEW

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

2"

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** #12-14 X 1 1/4" (GA) (2 EACH PURLIN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

PANELING CAP TRIM (SCT) RAKE ANGLE (A-20) HEIGHT CHANGE RAFTER 1/4-14 X 7/8" (12" C.C.)

EAVE STRUT

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION

STC-MSC Outset Gable Tail Height Change w Panel Below

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

PURLIN

* WALL PANEL HEIGHT CHANGE ANGLE (A-20-H)

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

RAKE SUPPORT (A-20-S) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL)

1/4-14 X 1 1/4" WT (12" C.C.) STC/MSC ROOF PANEL

PURLIN

***

PRE-GLUED THERMAL SPACER (NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

RAKE ANGLE (A-20) PURLIN

(2) #12-14 X 1 1/4"' PER CLOSURE

1

4 "

HEIGHT CHANGE RAFTER

2"

TOP VIEW

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

1/4-14 X 1 1/4" SHOULDER (24" C.C.)** PURLIN CLOSURE (GPC___) (PURLIN CLOSURE CLIPS NOT SHOWN) #12-14 X 1 1/4" (GA) (2 EACH PURLIN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EAVE STRUT

1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANELING CAP TRIM (SCT)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

*** DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION.

PURLIN CLOSURE INSTALLATION

STC-MSC Outset Gable Height Change w Field Bend Vertical Leg with Panel Below

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) 1/4-14 X 1 1/4" WT (12" C.C.) STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) PRE-GLUED THERMAL SPACER (NOT BY CHIEF) ***

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

* WALL PANEL

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

PURLIN CLOSURE (TYP.)

BL

RAKE SUPPORT (A-20-S) #12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) HEIGHT CHANGE ANGLE (A-20-H)

** IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT. * FIELD CUT BOTTOM OF WALL PANELS TO MATCH ROOF SLOPE. PROVIDE AIR GAP OF 1/4" MIN. AT BOTTOM OF PANEL TO AVOID CORROSION.

PURLIN

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN

1

4 "

HEIGHT CHANGE RAFTER

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

TOP VIEW

2"

*** DRAFTING NOTE:

RAKE ANGLE (A-20)

#12-14 X 1" PANCAKE HEAD (2 EACH PURLIN)

THERMAL SPACER TO BE USED WITH NO INSULATION.

1/4-14 X 1 1/4" SHOULDER (24" C.C.)**

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

PURLIN CLOSURE (GPC___) (PURLIN CLOSURE CLIPS NOT SHOWN #12-14 X 1 1/4" (GA) (2 EACH PURLIN)

EAVE STRUT

1/4-14 X 7/8" (12" C.C.)

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANELING CAP TRIM (SCT)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)

PURLIN CLOSURE INSTALLATION