STC MSC Roof Panel

STC-MSC Gable End Field Bend Vertical Leg - Taller Existing Building and Thermal Spacer

COUNTER FLASHING (NOT BY CHIEF)

TRI-BEAD TAPE SEALER SPECIAL TRIM TOP (SPT- ) CAULKING (NOT BY CHIEF)

1

L EXIST. B

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- )(BEFORE ASSEMBLING) (SEE INSET DETAIL)

FASTENER AT 12" C.C. (NOT BY CHIEF)

1/4-14 X 1 1/4" WT (12" C.C.)

STC/MSC ROOF PANEL (FIELD FORM 3" VERTICAL LEG TO FIT FINAL DIMENSION) THERMAL SPACER (NOT BY CHIEF)

HEIGHT CHANGE TRIM BOTTOM (GHMBF)

RAKE SUPPORT (A-20-T)

3"

PURLIN #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) 1/4-14 X 1 1/4" SHOULDER (24" C.C.) * RAKE ANGLE (A-20-B)

* IT IS IMPORTANT THAT FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT AND THAT THESE FASTENERS MUST NOT HIT THE PURLINS.

SIKA 511 CAULK IN LOCKFORM OF SPECIAL TRIM TOP (SPT- ) (BEFORE ASSEMBLING)