Composite Material, Rigid Board, R-Seal

STC-MSC Rigid Roof-Wall Gable Height Change Lead

NOTES: * Field cut bottom of wall panels to match roof slope. provide air gap of 1/4" min. at bottom of panel to avoid corrosion. ** It is important that fasteners are installed through the center of the slotted holes of the rake support. *** Insulation is representative. Erector shall refer to insulation manufacturer’s installation information for further details/direction. The erector is responsible for providing the final solution for installation, air tightness, and performance of the liner insulation system.

INSIDE CLOSURE HEIGHT CHANGE TRIM TOP (GHMTF) TRI-BEAD TAPE SEALER

BL

*** ___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF)

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING) (SEE INSET DETAIL) HEIGHT CHANGE TRIM BOTTOM (GHMBF) 1/4-14 X 1 1/4" WT (12" C.C.)

HEIGHT CHANGE ANGLE (PL-x) #12-14 X ____" * WALL PANEL

(6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

STC/MSC ROOF PANEL PRE-GLUED THERMAL SPACER RAKE SUPPORT (A-20-S)

DRAFTING NOTE: Include Corresponding Standard Details. - STC-MSC Height Change Isometric Details

* 1 4 "

(NOT BY CHIEF)

***___" RIGID CONTINUOUS INSULATION (NOT BY CHIEF) 1/4-14 X _____" W/O (EACH PURLIN) #12-14 X 1" PANCAKE HEAD (2 EACH PURLIN) RAKE SUPPORT (A-20-B) *1/4-14 X 1 1/4" SHOULDER (24" C.C.)

2"

INSULATION TO PANEL

PURLIN

SIKA 511 CAULK IN LOCKFORM OF HEIGHT CHANGE TRIM TOP (BEFORE ASSEMBLING)