Eave and Gable Extensions
MVF-MVP Gable Ext Lead End w FSP Soffit and Thermal Spacer
PURLIN
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
GABLE EXTENSION DIMENSION
* NOTE: This fastener must not hit the purlin. ** Field cut around purlins for attachment.
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
BL
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) DOUBLE BEAD TAPE MASTIC PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF) * 1/4-14 X 7/8" WT (6" C.C.) (2) #12-14 X 1 1/4" (EACH CLIP) (WALL COLOR)
GABLE TRIM (GTVC)
(2) #12-14 X 1 1/4" (WALL COLOR)
MVF/MVP ROOF PANEL
GABLE EXPANSION TRIM (GET) GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) 1/4-14 X 7/8" (12" C.C.) GABLE EXTENSION CHANNEL (GEC) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8"
PURLIN
PANEL CLIP WITH FASTENERS (TYP.) (SEE ROOF PANEL PLAN)
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
THERMAL SPACER (NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQUIRED) PURLIN CLOSURE (GPC)
TOP VIEW
1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) 1/8" X 3/8" BLIND RIVET (12" C.C.)
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) 1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS)
EAVE STRUT
FSP SOFFIT PANEL
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
** RAKE ANGLE (A-20)
INSIDE CLOSURE ***
PANEL CAP TRIM (SCT) 1/4-14 X 7/8" (12" C.C.) RAKE ANGLE (A-20-B)
*** DRAFTING NOTE: Inside closure must be provided on buildings with Liner Insulation System.
PURLIN CLOSURE INSTALLATION
WALL PANEL