Eave and Gable Extensions
MVF-MVP Gable Ext Tail End w CS Soffit and Thermal Spacer
1
PURLIN
ROOF PANEL CUT BACK DIMENSION
PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.
PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)
* NOTE: THIS FASTENER MUST NOT HIT THE PURLIN.
GABLE EXTENSION DIMENSION
CLOSURE CLIPS (GCC-1) (TYP.)
PURLIN CLOSURE (TYP.)
BL
#12-14 X 1 1/4" (2 EACH PURLIN) (WALL COLOR) * 1/4-14 X 1 1/4" WT (12" C.C.) DOUBLE BEAD TAPE MASTIC DOUBLE BEAD TAPE MASTIC PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION
GABLE TRIM SUPPORT (GTS) (10'-0" C.C.) #12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) (2) 1/4-14 X 7/8" PANEL CLIP w/FASTENERS GABLE TRIM (GTV) RAKE ANGLE (A-20-B) (2) #12-14 X 1 1/4"(WALL COLOR) EACH CLIP CLIP LOCATION FROM SL
PURLIN
PRE-GLUED THERMAL SPACER
1 3 4 "
(NOT BY CHIEF)
MVF/MVP ROOF PANEL PANEL CLIP w/FASTENERS PURLIN CLOSURE (GPC)
1"
PURLIN
(2) 1/8" X 3/8" BLIND RIVETS (TYP.)
#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN
(NOT BY CHIEF)
(2) #12-14 X 1 1/4"' PER CLOSURE
TOP VIEW
GABLE EXTENSION CHANNEL (GEC) 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)
CS SOFFIT PANEL 1/4-14 X 7/8" (12" C.C.) JAMB TRIM (JT) 1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT)
NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.
#12-14 X 1" PANCAKE HEAD EACH PURLIN EXTENSION FLASHING (EFC)
EAVE STRUT
INSIDE CLOSURE **
(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)
RAKE ANGLE (A-20-B) WALL PANEL
#12-14 X 1 1/4" (12" C.C.)
** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
PURLIN CLOSURE INSTALLATION