Eave and Gable Extensions
Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and CS Roof High Pitch
REFER TO GABLE SECTIONS FOR ROOF PANEL AND GABLE TRIM ATTACHMENTS AT THE BUILDING GABLE. *** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
NOTE: * PRE-DRILL TOP AND BOTTOM FLANGE OF EXTENSION BEAM FOR FASTENERS Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
1
SPECIAL CHANNEL (PL- )
* (2) #12-14 X 1 1/4" (WALL COLOR) (TYP.) EAVE EXTENSION BEAM * #12-14 X 1 1/4" (WALL COLOR) (AT PURLIN)
INSIDE CLOSURE
BL
***
#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
1"
INTERMEDIATE PURLIN
EAVE EXTENSION END PANEL
#12-14 X 1" PANCAKE HEAD (24" C.C.)
SOFFIT RAKE ANGLE (A-20-H)
** INSIDE CLOSURE
#12-14 X 1" PANCAKE HEAD
SOFFIT TRIM (VPST)
XXX' - X"
#12-14 X 1 1/4" GIRT ANGLE (XGA- )
1
4 "
PANEL SUPPORT (SSSP)
SOFFIT PURLIN
1/8" X 3/8" BLIND RIVET (12" C.C.)
FSP SOFFIT PANEL
**DRAFTING: INSIDE CLOSURE NOT REQ'D IF WALLS ARE "CS INSULATED"
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)