Eave and Gable Extensions
Eave Ext Horiz Soff Low Gable Ext - FSP Soffit Inset Gable and SS Roof Low Pitch
Refer to gable sections for roof panel and gable trim attachments at the building gable.
*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.
CUT THIS SECTION AT END OF EXTENSION
* STC/MSC ROOF: (2) #12-14 X 1 1/4" (WALL COLOR) (TYP.) MVF/MVP ROOF: (2) #12-14 X 1 1/4" (WALL COLOR) (TYP.)
SPECIAL CHANNEL (PL- )
SPECIAL CHANNEL (PL- ) XLGA-1 CLIP
BL
***
INSIDE CLOSURE
#12-14 X 1 1/4" PANCAKE HEAD (24" C.C.) (2) #12-14 X 1 1/4" PANCAKE HEAD
INTERMEDIATE PURLIN EAVE EXTENSION BEAM #12-14 X 1" PANCAKE HEAD
#12-14 X 1 1/4" (TYP) (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)
BL
EAVE EXTENSION PURLIN (FIELD NOTCH FOR SPECIAL CHANNEL) (2) #12-14 X 1 1/4" (WALL COLOR)
EAVE EXTENSION END PANEL #12-14 X 1" PANCAKE HEAD (24" C.C.)
** INSIDE CLOSURE
FRAMING CONDITION NOT SHOWN
SOFFIT RAKE ANGLE (A-20)
XXX' - X"
1
4 "
SOFFIT TRIM (VPST)
FSP SOFFIT PANEL
XBC-33 (4) 1/2" X 1 1/4" BOLTS EAVE EXTENSION BEAM SOFFIT RAKE ANGLE (A-20) #12-14 X 1" PANCAKE HEAD
PANEL SUPPORT (SSSP)
#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)
1/8" X 3/8" BLIND RIVET (12" C.C.)
**DRAFTING: INSIDE CLOSURE NOT REQ'D IF WALLS ARE "CS INSULATED" Provide air gap of 1/4" min. at bottom of panel to avoid corrosion.
NOTE: * PRE-DRILL TOP AND BOTTOM FLANGE OF EXTENSION BEAM FOR FASTENERS