Eave and Gable Extensions

STC-MSC Gable Ext Tail End-Field Bend Vertical Leg w FSP Soffit

**** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

***DRAFTING NOTE: THERMAL SPACER TO BE USED WITH NO INSULATION

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

1

CLOSURE CLIPS (GCC-1) (TYP.)

PANEL CLIP w/FASTENERS (TYP.) ** FIELD CUT AROUND PURLINS FOR ATTACHMENT.

PURLIN CLOSURE (TYP.)

GABLE EXTENSION DIMENSION

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-S) GABLE TRIM (GTM) NOTE: FIELD FORM A 3" VERTICAL ROOF PANEL LEG TO FIT FINAL DIMENSION

BL

#12-14 X 1" PANCAKE HEAD (2 PER PURLIN) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

PURLIN STC/MSC ROOF PANEL

PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION (NOT BY CHIEF)

PURLIN

** RAKE ANGLE (A-20)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN PRE-GLUED THERMAL SPACER *** (NOT BY CHIEF) PURLIN CLOSURE (GPC)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(2) #12-14 X 1 1/4"' PER CLOSURE

(2) 1/4-14 X 7/8"

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

TOP VIEW

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF) #12-14 X 1" PANCAKE HEAD (AT 1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET)

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

1/8" X 3/8" BLIND RIVET (12" C.C.) #12-14 X 1" PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) JAMB TRIM/SOFFIT TRIM (JTS)

EACH PURLIN PRIOR TO SOFFIT INSTALLATION)

1/4-14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B) INSIDE CLOSURE ****

EAVE STRUT

FSP SOFFIT PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

1/8" X 3/8" BLIND RIVET (12" C.C.)

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

WALL PANEL

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

PURLIN CLOSURE INSTALLATION