Eave and Gable Extensions

STC-MSC Gable Ext Tail End w FSP Soffit and Thermal Spacer

IF SUB-FRAMING AT GABLE EXTENSION EXCEEDS 4'-0 SPACING THEN AN A-20 ANGLE WILL BE SENT AND FIELD CUT AROUND PURLINS FOR ATTACHMENT. FASTENERS FOR ANGLE TO PURLIN AND SOFFIT TO ANGLE WILL BE SENT. CHANGE ANGLE AND FASTENERS TO "DIM" LAYER.

1

* NOTE: IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

PURLIN

GABLE EXTENSION DIMENSION

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

CLOSURE CLIPS (GCC-1) (TYP.)

BL

PURLIN CLOSURE (TYP.)

TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.)

* 1/4-14 X 1 1/4" SHOULDER (24" C.C.) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN) PRE-GLUED THERMAL SPACER FOR GABLE EXTENSION

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) RAKE SUPPORT (A-20-T) GABLE TRIM (GTM)

PANEL CLIP WITH FASTENERS

PURLIN

PURLIN STC/MSC ROOF PANEL

THERMAL SPACER

(NOT BY CHIEF)

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

(NOT BY CHIEF)

(2) 1/4-14 X 7/8"

PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

GABLE TRIM SUPPORT (GTS) (10'-0" C.C.)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR) #12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL) PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

TOP VIEW

GABLE EXPANSION TRIM (GET)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

1/4-14 X 7/8" (EACH RIB) (SOFFIT COLOR)

1/4-14 X 7/8" (12" C.C.)

#12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) GABLE EXTENSION CHANNEL (GEC) EXTENSION FLASHING (EF)

#12-14 X 1" PANCAKE HEAD (12" C.C.) (TYP.) #12-14 X 1"PANCAKE HEAD (AT EACH PURLIN PRIOR TO SOFFIT INSTALLATION) (TYP.) 1/8" X 3/8" BLIND RIVET (12" C.C.) JAMB TRIM/SOFFIT TRIM (JTS)

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

EAVE STRUT

INSIDE CLOSURE ***

** RAKE ANGLE (A-20) 1/8" X 3/8" BLIND RIVET (12" C.C.) FSP SOFFIT PANEL

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

RAKE ANGLE (A-20-B) PANEL CAP TRIM (SCT)

1/4-14 X 7/8" (12" C.C.)

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

WALL PANEL

** FIELD CUT AROUND PURLINS FOR ATTACHMENT.

NOTE: 26 GA FSP SOFFIT MUST ALWAYS HAVE 1/4-14 X 7/8" FASTENERS LOCATED AT RIBS AT END SUPPORTS. CHANGE FASTENERS TO "DIM" LAYER.

PURLIN CLOSURE INSTALLATION