High Profile Trim

STC-MSC Gable Ext Lead End High Profile Trim-AP Soffit and Thermal Spacer

1

PURLIN

PURLIN CLOSURE AT RIDGE IS TO BE FIELD CUT AND FASTENED TOGETHER WITH (2) 1/8" X 3/8" BLIND RIVETS.

GABLE EXTENSION DIMENSION

PURLIN CLOSURE (GPC2 OR GPC3) (TYP) (2) PURLIN CLOSURE CLIPS (GCC1) AT EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" EACH CLIP (2) 1/8" X 3/8" BLIND RIVETS (EACH CLIP)

*NOTE:IT IS IMPORTANT THAT 1/4-14 X 1 1/4" SHOULDER FASTENERS ARE INSTALLED THROUGH THE CENTER OF THE SLOTTED HOLES OF THE RAKE SUPPORT.

CLOSURE CLIPS (GCC-1) (TYP.)

#12-14 X 1 1/4" (12" C.C.) (TRIM COLOR) * 1/4-14 X 1 1/4" SHOULDER (24" C.C.) RAKE SUPPORT (A-20-T) GABLE TRIM (GTMH)

BL

PURLIN CLOSURE (TYP.)

#12-14 X 1" PANCAKE HEAD EACH PURLIN #12-14 X 1 1/4" (12" C.C.) (SOFFIT COLOR) TRI-BEAD TAPE SEALER 1/4-14 X 1 1/4" WT (12" C.C.) (NOT BY CHIEF) PRE-GLUED THERMAL SPACER

PANEL CLIP w/FASTENERS

PURLIN

PURLIN

STC/MSC ROOF PANEL

(2) 1/4-14 X 7/8"

(2) 1/8" X 3/8" BLIND RIVETS (TYP.)

THERMAL SPACER

(NOT BY CHIEF)

GABLE TRIM SUPPORT (GTS) (10'-0")

PURLIN CLOSURE (GPC)

(2) #12-14 X 1 1/4"' PER CLOSURE

PURLIN CLOSURE CLIP (GCC-1) (FIELD MODIFY CLIP AS REQ'D) (2) 1/8" X 3/8" BLIND RIVETS TO CONNECT EACH CLIP TO EACH PURLIN CLOSURE (2) #12-14 X 1 1/4" TO CONNECT EACH CLIP TO EACH PURLIN

1/4-14 X 7/8" (12" C.C.) GABLE EXPANSION TRIM (GET) #12-14 X 1" PANCAKE HEAD (2 PER PURLIN)

TOP VIEW

GABLE EXTENSION CHANNEL (GEC) EXTENSION GABLE FLASHING (EGFA) 1/4-14 X 7/8" (12" C.C.) **

NOTE: · Purlin closure is to be field cut between eave struts and purlins. · Closure clips may need to be field cut to fit in purlin and staggered so #12-14 X 1 1/4" fasteners don't interfere.

AP SOFFIT PANEL

#12-14 X 1 1/4" (6" C.C. for CS PANEL) (12" C.C. for AP PANEL)

#12-14 X 1 1/4" AT EACH PURLIN ROW (WALL COLOR )

1/4-14 X 7/8" (12" C.C.) (SOFFIT COLOR)

EAVE STRUT

** HIGH PROFILE TRIM SOFFITED GABLE EXT STC/ MSC

JAMB TRIM (JT) INSIDE CLOSURE ***

TRIM TYPE EGFA EFHP

PURLIN SIZE

L OR H SYSTEM

8

HIGH HIGH

(2) #12-14 X 1 1/4" (2) 1/8" X 3/8" BLIND RIVETS PURLIN CLOSURE CLIPS (GCC1)

PANEL SUPPORT TRIM (SSP) (TYP.) 1/4-14 X 7/8" (12" C.C.)

10

1/4 -14 X 7/8" (12" C.C.) PANEL CAP TRIM (SCT) RAKE ANGLE (A-20-B)

EGFA = EXTENSION GABLE FLASHING EFHP = EXT. FLASHING HIGH PROFILE

*** DRAFTING NOTE: INSIDE CLOSURE MUST BE PROVIDED ON BUILDINGS WITH LINER INSULATION SYSTEM.

PURLIN CLOSURE INSTALLATION